100 Amp Hour Battery Run Time Calculator
A 100 Ah 12 V battery runs a 5 amp load for 10 hours on lead-acid and 16 hours on lithium. Those figures apply a 50 percent depth of discharge to lead-acid and 80 percent to lithium, and shorter run times follow at higher currents once Peukert derating is included.
| Run time on one charge | |
| Time to a full discharge at this load | |
| Run time from the label alone (no derating) | |
| Capacity the battery delivered | |
| Energy stored at the pack voltage | |
| Energy you get out | |
| Load current drawn from the battery | |
| Inputs as entered | |
Run time = rated hours x (capacity / (load x rated hours))^Peukert, times the depth of discharge. Watts mode draws amps = watts / (inverter efficiency x volts). Exponent 1 gives the plain label math: hours = usable amp-hours / amps. Everything runs in your browser and nothing you type leaves the page.
Enter the load to see how long a 100 amp hour battery will run it, with depth of discharge and Peukert derating applied.
Key takeaways
- A 100 Ah battery holds 1,200 Wh at 12 volts, and 600 Wh is usable at 50 percent depth of discharge
- At 5 amps a 100 Ah lead-acid battery runs 10 hours; a lithium battery at 80 percent depth runs 16 hours
- Peukert derating cuts a 10 amp load from 5 hours on paper to 4.20 hours usable
- A 1,000 watt inverter load draws 92.59 amps at 12 volts and empties the usable half of the battery in about 16 minutes
- Discharges beyond about 80 percent of capacity shorten lead-acid battery life, per the Department of Energy primer
On this page
- What 100 amp hours means in practice
- The run time formula, with the Peukert correction
- Worked example: a 5 amp load on a 100 Ah battery
- Worked example: a 10 amp load, where Peukert bites
- Depth of discharge: how much of the 100 Ah you can spend
- Run time by load on a 100 Ah battery
- Watts, inverters and real loads
- How to use this calculator
What 100 amp hours means in practice
A 100 Ah battery stores 100 amp-hours of charge, which at 12 volts is 1,200 watt-hours, or 1.2 kilowatt-hours. That is the raw energy in the box. How long it lasts depends on three things: the load you put on it, how far down you are willing to drain it, and how the battery behaves at the current you draw.
The 100 Ah figure itself comes from a test. Manufacturers rate capacity at a fixed discharge time, usually 20 hours, so a 100 Ah battery is the battery that delivers 5 amps for 20 hours before it hits its cutoff voltage. That rating is the anchor for every run time estimate. Drain it at 5 amps and the label math works. Drain it at 20 amps and the battery delivers less than its label says, because the chemical reaction inside cannot keep up.
For a 12 volt pack, 100 Ah is the size of a common deep-cycle marine battery, a mid-size RV house battery, or a small solar storage bank. In lithium, the same 100 Ah label fits in a much lighter case and usually gives up more of its rated capacity before the low-voltage cutoff. Both are called 100 Ah; they do not behave the same way.
The run time formula, with the Peukert correction
The plain estimate is hours = usable amp-hours divided by load amps. Usable amp-hours is capacity times depth of discharge. A 100 Ah battery drawn to 50 percent gives you 50 Ah, so a 5 amp load runs 10 hours and a 10 amp load runs 5 hours.
The plain estimate breaks down at high currents. Peukert's law, published in 1897 and still the standard first correction, says the capacity a lead-acid battery can deliver falls as the discharge current rises. The Department of Energy storage guide describes the effect directly: as the discharge rate increases, the battery's available energy capacity decreases. The usual form, as detailed in a Stanford battery modeling paper, is I raised to n, times T, equals a constant, where I is current, T is time and n is the Peukert exponent. Solved for time at a rated capacity C and rated hour rate H, it becomes T = H times (C divided by (I times H)) raised to n.
The exponent is the tuning knob. A value of 1 removes the correction and returns the label math. Flooded lead-acid sits around 1.2 to 1.3, AGM and gel around 1.1 to 1.2, and lithium iron phosphate close to 1.05, which is why lithium run times track the simple division far more closely. Then multiply by depth of discharge to get the time you can use in practice.
Worked example: a 5 amp load on a 100 Ah battery
Take a 100 Ah flooded lead-acid battery at 12 volts, rated at the 20 hour rate, with a 5 amp load. That 5 amps is exactly the rated current, so the Peukert correction does nothing: 20 times (100 divided by 100) raised to 1.25 is 20 hours to a full discharge. At 50 percent depth of discharge you get 10 hours of run time, using 50 Ah and 600 Wh of the 1,200 Wh stored.
The same 5 amp load on a 100 Ah lithium iron phosphate battery at 80 percent depth runs 16 hours, because the full-discharge time is still 20 hours but you are allowed to spend 80 Ah instead of 50. That is 960 Wh delivered from the same nominal capacity, a 60 percent gain in usable energy from chemistry and depth of discharge alone.
Put a number on the load and the picture gets concrete: 5 amps at 12 volts is 60 watts, about a laptop charger, a small fan or a few LED lights. A 100 Ah lead-acid battery runs that for a 10 hour night and still has half its charge in reserve. Add a 60 W fridge cycling on and off and the average draw rises, so the run time falls in proportion.
Worked example: a 10 amp load, where Peukert bites
Double the load to 10 amps on the same lead-acid battery. Label math says 50 usable amp-hours divided by 10 amps is 5 hours. The Peukert form says 20 times (100 divided by 200) raised to 1.25, which is 8.41 hours to a full discharge, so the usable time at 50 percent is 4.20 hours, or 4 hours 12 minutes. The gap between 5 hours on paper and 4.20 hours in practice is the effect in one line.
Push harder and it widens. At 30 amps, label math promises 1.67 hours; Peukert gives 2.13 hours to full discharge and 1.06 hours usable, about 1 hour 4 minutes. At 50 amps the battery is down to 0.56 hours usable, roughly 34 minutes, against a paper figure of 1 hour. A trolling motor, a microwave through an inverter or a winch all sit in this range, which is why owners who size a bank from label amp-hours come up short.
At low currents the correction runs the other way. A 2 amp load gets 31.44 usable hours, not the 25 hours label math predicts, because a slow discharge lets the chemistry keep up and recovers capacity that a fast draw would leave behind. Peukert is a curve, not a penalty.
Depth of discharge: how much of the 100 Ah you can spend
Depth of discharge is the share of capacity you take out before recharging. A 50 percent limit on a 100 Ah battery means you treat it as a 50 Ah battery and leave the other half in place. That habit is what separates a battery that lasts several hundred cycles from one that fails inside two years.
The Department of Energy's primer on lead-acid storage batteries notes that discharges beyond about 80 percent of capacity can be expected to shorten battery life, and the same document puts flooded battery life at 10 years or longer with proper maintenance. The practical numbers most off-grid users settle on are 50 percent for flooded lead-acid, 50 percent for AGM, and 80 percent for lithium iron phosphate, whose battery management system usually enforces the floor for you.
Depth of discharge is a trade, not a rule handed down. Drawing to 80 percent instead of 50 percent gives 60 percent more run time on the same battery, at the cost of fewer cycles before replacement. If the battery is cheap and cycles are rare, that trade can win. For a daily solar cycle, the 50 percent habit usually costs less per kilowatt-hour over the life of the bank.
The table converts those limits into usable hours on one 100 Ah battery at a 5 amp load, using the Peukert exponents above and a 20 hour rating.
| Chemistry | Depth of discharge | Usable capacity | Usable energy at 12 V | Run time at 5 A |
|---|---|---|---|---|
| Flooded lead-acid | 50% | 50 Ah | 600 Wh | 10 h 00 min |
| Flooded lead-acid | 80% | 80 Ah | 960 Wh | 16 h 00 min |
| AGM or gel | 50% | 50 Ah | 600 Wh | 10 h 00 min |
| LiFePO4 | 80% | 80 Ah | 960 Wh | 16 h 00 min |
| LiFePO4 | 90% | 90 Ah | 1,080 Wh | 18 h 00 min |
| LiFePO4 | 100% | 100 Ah | 1,200 Wh | 20 h 00 min |
Two rows deserve a second look. Lithium at 100 percent is a spec sheet figure rather than a plan, because most LiFePO4 banks ship with a management system that stops discharge near 90 percent and daily trips to the floor cost cycles. AGM at 50 percent matches flooded on hours, and the real difference between the two shows up in price and cycle life, not in run time.
Run time by load on a 100 Ah battery
The table shows one 100 Ah flooded lead-acid battery at 12 volts, rated at the 20 hour rate, with a Peukert exponent of 1.25 and a 50 percent depth of discharge. The label column is the simple division most people do in their heads. The last column is what the battery gives up in test conditions.
| Load | Label math | Time to full discharge | Usable at 50% depth |
|---|---|---|---|
| 2 A | 25.00 h | 62.87 h | 31.44 h |
| 5 A | 10.00 h | 20.00 h | 10.00 h |
| 10 A | 5.00 h | 8.41 h | 4.20 h |
| 20 A | 2.50 h | 3.54 h | 1.77 h |
| 25 A | 2.00 h | 2.67 h | 1.34 h |
| 50 A | 1.00 h | 1.12 h | 0.56 h |
Notice where the label math is honest: at 5 amps, the rated current, the two agree. Everywhere else they part company, and the error grows with the load. A 50 amp load gets 34 minutes of usable time, not the hour the label implies, which is a 44 percent shortfall on a load a small inverter can pull without warning.
Watts, inverters and real loads
Most loads are labeled in watts, not amps, and the calculator converts for you. On a DC circuit the current is watts divided by volts, so 60 watts at 12 volts draws 5 amps. Through an inverter the math picks up one more term: current from the battery is watts divided by inverter efficiency divided by volts. A 90 percent efficient inverter running a 60 watt AC load pulls 5.56 amps from a 12 volt battery, and the Peukert penalty at that slightly higher current trims the usable time to 8 hours 46 minutes instead of 10 hours.
Large inverter loads get ugly fast. A 1,000 watt load through a 90 percent inverter draws 92.59 amps at 12 volts, close to a 1C rate on a 100 Ah battery. Peukert time to full discharge is 0.52 hours, and at 50 percent depth you get about 16 minutes. A 100 Ah battery is not a serious match for a 1,000 watt inverter, no matter what the label suggests.
Two more habits keep estimates honest. Use the average draw for cycling loads, not the peak, since a fridge that pulls 5 amps while running and runs a third of the time averages 1.7 amps. And keep the inverter's idle draw in the total: a 20 watt standby load left on all night spends 160 watt-hours overnight, which is over a quarter of the 600 Wh a 12 volt, 100 Ah lead-acid bank gives up at 50 percent depth.
The table runs one 12 volt, 100 Ah lead-acid battery at 50 percent depth through a 90 percent efficient inverter at common load sizes.
| AC load | Current from the battery | Time to full discharge | Usable time at 50% |
|---|---|---|---|
| 60 W | 5.56 A | 17.53 h | 8 h 46 min |
| 150 W | 13.89 A | 5.58 h | 2 h 47 min |
| 300 W | 27.78 A | 2.34 h | 1 h 10 min |
| 600 W | 55.56 A | 0.99 h | 0 h 30 min |
| 1,000 W | 92.59 A | 0.52 h | 0 h 16 min |
| 1,500 W | 138.89 A | 0.31 h | 0 h 09 min |
Read the last row as a warning. A 1,500 watt load flattens the usable half of this battery in about nine minutes, well before the inverter reaches its own low voltage cutoff, and the current draw sits above 1C. Size the battery bank from the loads you run in practice, and treat the inverter label as a ceiling rather than a target.
How to use this calculator
Enter the capacity, the pack voltage and the load. Switch the load between amps and watts depending on the label; in watts mode the inverter efficiency input converts to battery current. Pick a battery type to load its usual depth of discharge and Peukert exponent, or set both by hand. The rated hour rate defaults to 20, which is what most 100 Ah labels use.
The results give the usable run time in hours and minutes, the time to a full discharge, the label-math estimate for comparison, the amp-hours and watt-hours you spend, and the current drawn from the battery. The label-math row is there so you can see how much the derating changed the answer.
What the model leaves out: temperature (a cold battery gives up less), age (a three-year-old bank may hold 80 percent of its rating), the low-voltage cutoff of your inverter, and loads that vary minute to minute. Treat the result as a planning figure with a margin, not a promise, and check the battery manufacturer's data sheet for the Peukert exponent and the recommended depth of discharge for your exact model.
Frequently asked questions
How long will a 100 amp hour battery run a 5 amp load?
On a 12 volt lead-acid battery at 50 percent depth of discharge, 10 hours, since 5 amps is the rated current at the 20 hour rate and 50 of the 100 amp-hours are usable. A lithium battery at 80 percent depth runs 16 hours on the same load.
How many watt hours is a 100 Ah battery?
100 Ah at 12 volts is 1,200 Wh, or 1.2 kWh. At 24 volts the same capacity holds 2,400 Wh, and at 48 volts 4,800 Wh. Watt-hours are the better unit when you compare batteries of different voltages.
How long will a 100 Ah battery run a 12 volt fridge?
A fridge that averages 4 amps draws 96 watts. On a 100 Ah lead-acid battery at 50 percent depth, Peukert time to full discharge is 26.43 hours, so usable run time is 13.22 hours. A 100 Ah lithium battery at 80 percent depth runs about 20 hours.
How long will a 100 Ah battery run a 1,000 watt inverter?
A 1,000 watt load through a 90 percent efficient inverter pulls 92.59 amps from a 12 volt battery. That is close to a 1C rate, and the usable time at 50 percent depth is about 16 minutes. Size the bank for the load, not the other way around.
What is the Peukert effect?
Peukert's law says a lead-acid battery delivers less capacity at higher discharge currents. It is written I^n x T = constant, where n is the Peukert exponent. A value of 1 means no effect, 1.25 is typical for flooded lead-acid, and 1.05 is typical for lithium iron phosphate.
Why does my 100 Ah battery die faster than 100 divided by the load?
Three reasons: Peukert derating at high current, a depth-of-discharge limit that keeps part of the capacity off limits, and losses from cold, age or an inverter. A 20 amp load on a 100 Ah lead-acid battery gives 1.77 usable hours at 50 percent depth, not the 2.5 hours label math predicts.
How long does a 100 Ah battery last at 20 amps?
A flooded lead-acid battery at 50 percent depth gives 1.77 hours, about 1 hour 46 minutes. Time to a full discharge is 3.54 hours with a Peukert exponent of 1.25. A lithium battery at 80 percent depth runs about 3.7 hours on the same load.
Should I use 50 percent or 80 percent depth of discharge?
For daily cycling, 50 percent is the usual choice on lead-acid and AGM, and 80 percent is common on lithium. Drawing a lead-acid battery past about 80 percent of its capacity shortens its life, according to the Department of Energy's lead-acid primer.
Does a 100 Ah lithium battery last longer than a 100 Ah lead-acid battery?
Per charge, yes: 80 usable amp-hours against 50, and a Peukert exponent near 1.05 instead of 1.25, so a 10 amp load runs 8 hours on lithium against 4.20 hours on lead-acid. Lithium also usually delivers more cycles before replacement.
How do I convert watts to amps for this calculator?
Divide watts by volts. A 60 watt load at 12 volts is 5 amps. Through an inverter, divide by the efficiency too: 60 watts at 90 percent efficiency and 12 volts is 5.56 amps.
Is the 20 hour rate the same for every 100 Ah battery?
No. Most 100 Ah deep-cycle labels use the 20 hour rate, but some rate at 100 hours, and a battery rated at the 100 hour rate delivers less at 20 hours. Check the label for the hour rate before you trust the number, and set the rated hour rate input to match.
Can I run a 100 Ah battery down to zero?
You can, but you should not do it often. A full discharge stresses lead-acid plates and can leave a lithium pack's management system to cut the load without warning. A 50 percent floor on lead-acid and 80 percent on lithium is the common compromise.
How is run time different from battery life?
Run time is how many hours one charge gives you. Battery life is how many charge cycles, or years, the battery survives before it holds too little capacity. Deeper discharges shorten life while lengthening each run, so the two move in opposite directions.
Spotted a wrong number or a broken result?
More Date Time tools
- 1 Hour From Now
- 1 Month Notice Period Calculator
- 1 Weeks From Today
- 1/4 Mile Time Calculator
- 1/8 Mile Time Calculator
- 10 Hours Ago
- 10 Hours From Now
- 10 Minutes Ago
- 10 Months From Today
- 10 Weeks Ago From Today
- 10 Weeks From Today
- 100 Day Calculator
- 100 Days Calculator
- 11 Hours Ago
- 11 Hours From Now
- 11 Months From Today
Fee schedules, rates and rules change without notice. Always confirm important figures with the official source before you rely on them.