100 Amp Wire Size Calculator
At 75 C terminations a 100 amp circuit takes 3 AWG copper or 1 AWG aluminum. A single family dwelling service or whole house feeder may drop to 4 AWG copper or 2 AWG aluminum under the NEC 83 percent rule, while a 200 foot run moves up to at least 1 AWG copper to hold voltage drop near 3 percent.
Size the wire for a 100 amp circuit: enter the load, the one way run length and the voltage, and the table picks the smallest copper or aluminum size that carries the amps and holds voltage drop near 3 percent.
| Ampacity required | |
| Smallest wire by ampacity | |
| Voltage drop on that wire | |
| Smallest wire holding 3 percent drop | |
| Recommended size (larger of the two) | |
| Max one way length at 3 percent for that wire | |
| Equipment grounding conductor | |
| Same table row in the other metal |
Sizing follows the NEC Table 310.16 ampacity columns with a 3 percent voltage drop target. Derating for bundling, ambient heat and conduit fill is not applied here. All calculations run in your browser, and nothing you enter is uploaded.
Enter the load, run length, voltage and material to size a 100 amp circuit: ampacity from NEC Table 310.16, voltage drop at 3 percent, and the ground size.
Key takeaways
- 3 AWG copper or 1 AWG aluminum carries 100 amps at the 75 C column of NEC Table 310.16
- A dwelling service or whole house feeder may drop to 4 AWG copper or 2 AWG aluminum because NEC 310.12 allows 83 percent sizing (100 x 0.83 = 83 amps)
- Voltage drop moves the size up: 3 AWG copper holds 3 percent only to about 147 feet at 240 volts, so a 200 foot run takes 1/0 copper
- Most breaker lugs are rated 75 C, so the 90 C rating of THHN wire is a derating starting point, not the size you buy
- A 100 amp circuit needs an 8 AWG copper or 6 AWG aluminum equipment grounding conductor under NEC 250.122
On this page
The short answer for 100 amps
For a general 100 amp circuit at the 75 C column of NEC Table 310.16, the wire is 3 AWG copper or 1 AWG aluminum. Those are the smallest sizes whose ampacity reaches 100 amps, and most breaker lugs and panel terminations carry a 75 C rating, so the 75 C column is the one that counts. Copper 4 AWG sits just below the mark at 85 amps and aluminum 2 AWG sits at 90 amps, so neither protects a plain 100 amp feeder without one of the exceptions below.
| Situation | Copper | Aluminum |
|---|---|---|
| 100 amp feeder or subpanel, 75 C terminations | 3 AWG | 1 AWG |
| Dwelling service or whole house feeder (83 percent rule) | 4 AWG | 2 AWG |
| 100 amp continuous load (125 percent sizing) | 1 AWG | 2/0 AWG |
| Run near 200 feet held to 3 percent voltage drop | 1 AWG | 2/0 AWG |
| Lugs rated 60 C only | 1 AWG | 1/0 AWG |
The rows interact. A garage subpanel fed on a 150 foot run takes at least 2 AWG copper or 1/0 aluminum, not the dwelling rule sizes, because a feeder that serves a garage does not serve the entire dwelling load. Start from the row that matches the job, then check voltage drop before buying wire.
Why 100 amps does not always mean a 100 amp wire
The NEC sizes conductors to the load, and the load rules cut in two directions. A feeder protected by a 100 amp breaker needs conductors rated for at least 100 amps, which is where 3 AWG copper comes from. But a load that runs for three hours or more counts as continuous, and 210.19(A)(1) and 215.2(A)(1) require the conductor to carry 125 percent of a continuous load: 100 x 1.25 = 125 amps, which pushes the copper up to 1 AWG (130 amps at 75 C) and the aluminum up to 2/0 (135 amps).
The other direction is the dwelling allowance. A single family service or a feeder that carries the whole dwelling load may be sized at 83 percent of the rating under NEC 310.12, so a 100 amp service needs conductors good for 100 x 0.83 = 83 amps. Copper 4 AWG at 85 amps and aluminum 2 AWG at 90 amps clear that bar, which is why 4 AWG copper shows up in so many 100 amp service installs.
What the wire never gets to do is sit below its breaker with no exception. Aluminum 2 AWG at 90 amps under a 100 amp breaker works only where the 83 percent rule applies or where the calculated load is at or below 90 amps and the local inspector accepts it. When in doubt, the next size up costs little and ends the argument.
NEC Table 310.16: the numbers behind the answer
Table 310.16 of the 2023 NEC lists allowable ampacities for insulated conductors in raceway or cable. The columns matter: the 60 C column applies to old style terminations, the 75 C column matches most modern breakers and lugs, and the 90 C column exists mainly as a starting point for derating, because 110.14(C) ties the usable rating to the coolest termination in the circuit.
| Size | Copper 60 C | Copper 75 C | Aluminum 75 C |
|---|---|---|---|
| 4 AWG | 70 A | 85 A | 65 A |
| 3 AWG | 85 A | 100 A | 75 A |
| 2 AWG | 95 A | 115 A | 90 A |
| 1 AWG | 110 A | 130 A | 100 A |
| 1/0 AWG | 125 A | 150 A | 120 A |
| 2/0 AWG | 145 A | 175 A | 135 A |
Reading the table answers the common questions at a glance. Aluminum needs to sit about two sizes above copper for the same job, which the rows show: copper 3 AWG and aluminum 1 AWG both reach 100 amps. The 90 C numbers are higher, yet a wire picked from the 90 C column is still wrong if any lug on the path is rated 75 C. The full table lives in NFPA 70, the National Electrical Code (NFPA, free online access).
Voltage drop on a long 100 amp run
Ampacity is only half the sizing story; distance adds resistance loss. For a single phase run the drop is VD = 2 x K x I x L / CM, where K is 12.9 for copper and 21.2 for aluminum at 75 C, I is the current in amps, L is the one way length in feet and CM is the conductor area in circular mils (3 AWG copper is 52,620 circular mils). The informational notes behind 210.19 and 215.2 point to 3 percent for a single run as the working target.
Worked example: 100 amps over 100 feet of 3 AWG copper at 240 volts. The drop is 2 x 12.9 x 100 x 100 / 52620 = 4.9 volts, about 2.0 percent of 240. Stretch the same run to 150 feet and the drop grows to 7.4 volts, 3.1 percent, over the target. The fix is size, not heroics: each step up in gauge adds roughly 25 percent more area.
| Conductor | Max one way feet at 3 percent (240 V, 100 A) |
|---|---|
| 3 AWG copper | 147 ft |
| 2 AWG copper | 185 ft |
| 1 AWG copper | 233 ft |
| 1/0 copper | 295 ft |
| 1 AWG aluminum | 142 ft |
| 1/0 aluminum | 179 ft |
| 2/0 aluminum | 226 ft |
At 120 volts the same amps lose twice the percentage per foot, so the 3 AWG copper limit falls to about 73 feet. The calculator on this page runs these numbers for any length you enter and shows the size it picks when voltage drop, not ampacity, decides.
The 83 percent rule for a dwelling service
NEC 310.12 (310.15(B)(7) in the 2017 and 2020 editions) lets service conductors and whole house feeders of a single phase dwelling be sized at 83 percent of the service rating, on the logic that a residence never draws its full panel rating on every wire at once. For a 100 amp service the math is 100 x 0.83 = 83 amps, and two standard sizes clear it: copper 4 AWG at 85 amps and aluminum 2 AWG at 90 amps.
| Conductor run | 83 percent applies? | Copper size | Aluminum size |
|---|---|---|---|
| Service entrance to the main panel | Yes | 4 AWG | 2 AWG |
| Feeder carrying the entire dwelling load | Yes | 4 AWG | 2 AWG |
| Feeder to a garage, shop or addition | No | 3 AWG | 1 AWG |
| Commercial or industrial feeder | No | 3 AWG | 1 AWG |
The limit matters in practice: a detached garage or an addition has its own load and its own panel, so its feeder is a plain 100 amp feeder and takes 3 AWG copper or 1 AWG aluminum. Inspectors apply the rule by edition year, and some jurisdictions amend it, so confirm the edition your permit is written against. Workplace wiring under OSHA 29 CFR 1910.304 follows the same conductor sizing logic for the sites it covers.
Grounds, neutrals and terminations
Three supporting conductors ride along with the hots. The equipment grounding conductor for a 100 amp overcurrent device is 8 AWG copper or 6 AWG aluminum under NEC 250.122, and its size follows the breaker rating, not the run length. The grounded conductor, the neutral, carries only the imbalance between the two hots of a 120/240 volt feeder, so 220.61 allows it to be smaller than the hots when the load calculation supports it, though services are commonly pulled at full size for margin.
| OCPD rating | Copper ground (250.122) | Aluminum ground |
|---|---|---|
| 60 A | 10 AWG | 8 AWG |
| 100 A | 8 AWG | 6 AWG |
| 125 A | 8 AWG | 6 AWG |
| 150 A | 6 AWG | 4 AWG |
Terminations decide the rest. Aluminum lugs need connectors listed AL/CU, torque to the marking on the equipment, and a coat of antioxidant joint compound on the exposed conductor. Cable assemblies make the shopping list short: copper SER in 3-3-3-5 or aluminum SER in 1-1-1-3 covers a plain 100 amp feeder, while the widely sold 2-2-2-4 aluminum SER carries 90 amps at 75 C and belongs only where the dwelling 83 percent rule applies or the load calculation comes in at or below 90 amps.
How to use the calculator, and what it leaves out
Enter the load in amps (100 is the default), the one way run length, the system voltage, the conductor material and the termination temperature, and check the continuous box if the load runs three hours or more. The results table shows the smallest wire that carries the ampacity, the voltage drop on that wire over your run, the smallest wire that holds 3 percent, the recommended pick between the two, the maximum length at 3 percent and the grounding conductor size. Change any input and the table updates.
The calculator leaves out the parts of Article 310 that need judgment: more than three current carrying conductors in a raceway trigger the 80 percent adjustment of 310.15(C)(1), ambient temperatures above 30 C (86 F) need the correction factors of Table 310.15(B)(1), and conduit fill beyond 40 percent follows Chapter 9. Local amendments, permit inspections and the edition your state adopts all sit on top of the tables shown here. For a service upgrade or anything inside the panel, the figures on this page are a planning aid; the installation itself belongs to a licensed electrician.
Frequently asked questions
What size wire do I need for 100 amps?
3 AWG copper or 1 AWG aluminum at the 75 C column of NEC Table 310.16. A dwelling service or whole house feeder may drop to 4 AWG copper or 2 AWG aluminum under the 83 percent rule of NEC 310.12.
Is 2 AWG aluminum good for 100 amps?
Only in the dwelling case. 2 AWG aluminum is rated 90 amps at 75 C, which clears the 83 amps a 100 amp dwelling service needs under 310.12, but it does not carry a plain 100 amp feeder.
Is 2 AWG copper good for 100 amps?
Yes. 2 AWG copper is rated 115 amps at 75 C, above the 100 amp mark, and it is a common pick for runs past the point where 3 AWG fails the voltage drop target.
How far can you run 3 AWG copper at 100 amps?
About 147 feet one way at 240 volts while holding 3 percent voltage drop. Past that, step up to 2 AWG (185 feet), 1 AWG (233 feet) or 1/0 copper (295 feet).
What is the voltage drop formula for a 100 amp feeder?
VD = 2 x K x I x L / CM, with K at 12.9 for copper and 21.2 for aluminum, I in amps, L the one way length in feet and CM the circular mil area. For 3 AWG copper at 100 feet: 2 x 12.9 x 100 x 100 / 52620 = 4.9 volts.
What size ground wire for a 100 amp circuit?
8 AWG copper or 6 AWG aluminum under NEC 250.122. The ground size follows the breaker rating, not the run length.
Does a 100 amp continuous load change the wire size?
Yes. A load running three hours or more counts as continuous, and the conductor must carry 125 percent: 100 x 1.25 = 125 amps, which takes 1 AWG copper or 2/0 aluminum at 75 C.
Why size from the 75 C column when THHN is 90 C?
Because NEC 110.14(C) ties the ampacity to the weakest termination in the circuit, and most breaker lugs are listed at 75 C. The 90 C figure is the starting point for derating, not the size you install.
What size wire for a 100 amp sub panel in a garage?
3 AWG copper or 1 AWG aluminum for a short run, sized up for voltage drop on longer runs. The 83 percent dwelling rule does not apply to a garage subpanel because it does not carry the entire dwelling load.
Is 2-2-2-4 aluminum SER enough for 100 amps?
Only where the 83 percent rule applies or the calculated load is 90 amps or less. Its two hots are 2 AWG aluminum at 90 amps at 75 C; a general 100 amp feeder wants 1-1-1-3 aluminum SER or larger.
What size wire for 100 amps at 120 volts instead of 240?
The ampacity answer is the same, but the voltage drop percentage doubles for the same feet and amps, so 3 AWG copper holds 3 percent only to about 73 feet at 120 volts.
Does the neutral on a 100 amp feeder need to match the hots?
Not always. NEC 220.61 lets the grounded conductor carry only the unbalanced load, so a smaller neutral is permitted when the calculation supports it, though services are commonly pulled at full size for margin.
Spotted a wrong number or a broken result?
More Tech tools
- Amp-Hour Calculator
- Amps to kVA Calculator
- Audio File Size Calculator: WAV, MP3 and Storage Time
- Bandwidth Calculator
- Battery Charge Time Calculator
- Battery Life Calculator
- Bits to Bytes Converter
- CFM Calculator
- Capacitance
- Capacitor Calculator
- Current Calculator
- Data Transfer Calculator
- Data Usage Calculator
- Download Time Calculator
- Downtime Cost Calculator
- Electric Charge Calculator
Fee schedules, rates and rules change without notice. Always confirm important figures with the official source before you rely on them.