kVA to kW Calculator

A 100 kVA supply at a power factor of 0.8 delivers 80 kW of real power. Multiply kVA by the power factor, so 100 x 0.8 = 80. The same hardware at a power factor of 1.0 delivers 100 kW, which is 25 percent more usable power.

Enter kVA and the power factor, or start from kW and work backwards, and get real power, reactive kVA and the line current at your voltage.

By the Lelifi editors ·

Key takeaways

Real power in kW from the same 100 kVAPower factor 0.550 kWPower factor 0.770 kWPower factor 0.880 kWPower factor 0.990 kWPower factor 1.0100 kW
The same 100 kVA rating yields anywhere from 50 to 100 kW depending on the power factor of the load.
Line current in amps at 480 V, three phase15 kVA18.04 A30 kVA36.08 A45 kVA54.13 A75 kVA90.21 A
Full-load line current at 480 V three phase, from a 15 kVA unit up to 75 kVA.
On this page
  1. Apparent power and real power are not the same number
  2. The single phase formula: kVA x power factor
  3. Three phase: where the 1.732 comes from
  4. What a 100 kVA unit delivers at each power factor
  5. Working backwards from kW to kVA
  6. Typical power factors by load
  7. Why demand is billed in kVA

Apparent power and real power are not the same number

Volts times amps gives volt-amperes, and a thousand of them is one kVA. That is apparent power: the total that the wires, the breaker and the transformer have to carry. The kilowatts that turn a motor or heat a room are real power, and in an alternating current circuit the two only match when the load is a pure resistance.

Motors, transformers, compressors and old magnetic ballasts pull current slightly out of step with the voltage. The current sloshes back and forth without doing work, and the utility still has to size for it. That extra is reactive power, measured in kVAR, and the three quantities form a right triangle: 100 kVA at 0.8 power factor is 80 kW and 60 kVAR, because the square root of 100 squared minus 80 squared is 60.

Power factor is real power divided by apparent power, so it runs from 0 to 1 and never above 1. A power factor of 1 means every kVA is doing useful work. A power factor of 0.5 means half of what you paid to install is moving current that produces no output at all.

The single phase formula: kVA x power factor

For a single phase load the conversion is one multiplication:

Two runs with real numbers. A 100 kVA generator nameplate at 0.8 gives 100 x 0.8 = 80 kW. The same generator at 0.95 gives 100 x 0.95 = 95 kW, so the rating on the label and the usable output are two different facts, and the power factor is what connects them.

The reverse direction matters when you size equipment from a load list. A 45 kW load at a power factor of 0.75 needs 45 / 0.75 = 60 kVA of apparent capacity, not 45. Buy a 45 kVA unit for that load and it will be overloaded on current long before it reaches its kW rating. This is the mistake that turns a cheap transformer into an expensive one.

Three phase: where the 1.732 comes from

Three phase power adds a factor of the square root of 3, which is 1.732, because three waveforms 120 degrees apart share the same conductors. With kVA given as the total for all three phases:

QuantitySingle phaseThree phase
Real powerkW = kVA x PFkW = 1.732 x kVA x PF
Apparent powerkVA = kW / PFkVA = kW / (1.732 x PF)
Line currentamps = kVA x 1000 / voltsamps = kVA x 1000 / (1.732 x volts)

A 75 kVA transformer on a 480 V three phase service carries 75,000 / (1.732 x 480) = 90.21 amps per line at full load. If the load runs at a power factor of 0.85, the real power that unit can deliver is 75 x 0.85 = 63.75 kW, and the reactive part is 75 x 0.527 = 39.5 kVAR. The 1.732 belongs in the current calculation only, because the kVA figure already counts all three phases.

Folding the root three in twice is the common error in this conversion. When someone quotes a three phase kVA, all three phases are already counted, and multiplying by 1.732 again inflates the answer by 73 percent.

What a 100 kVA unit delivers at each power factor

The same apparent rating produces less and less real power as the power factor falls. The table holds kVA at 100 and moves only the power factor.

Power factorReal power (kW)Reactive power (kVAR)Share of kVA doing work
1.01000100 percent
0.959531.2295 percent
0.99043.5990 percent
0.8806080 percent
0.77071.4170 percent
0.55086.650 percent

At 0.8, one fifth of the capacity is stranded: you paid for 100 kVA, the breaker and the copper are sized for 100 kVA, and only 80 kW can go to work. The reactive column is the part the meter measures but the load never uses.

This is why a data center will pay extra for a UPS with a unity output rating. Moving from 0.8 to 1.0 on a 100 kVA unit frees 20 kW, which is a quarter more real capacity from the same footprint, the same switchgear and the same cooling.

Working backwards from kW to kVA

Load schedules are written in kW, because that is what the equipment consumes, and every purchase is quoted in kVA. Divide to cross over. A 250 kW load at a power factor of 0.92 needs 250 / 0.92 = 271.74 kVA, and on a 480 V three phase service that is 271,740 / (1.732 x 480) = 326.85 amps per line.

A smaller case shows the same steps. A 15 kVA load at 208 V three phase draws 15,000 / (1.732 x 208) = 41.64 amps. At 480 V the same 15 kVA draws only 18.04 amps, which is why commercial buildings run distribution at the higher voltage and step down at the equipment.

If the load list gives amps and volts instead of kW, go through apparent power first: 1.732 x volts x amps / 1000 gives kVA, then multiply by the power factor for kW. Skipping the power factor gives you the size of the wire you need, not the size of the generator you need.

Typical power factors by load

The power factor is a property of the load, not of the supply, so the honest answer to "what number do I type" comes from the equipment. Some anchors are solid, and the Department of Energy's motor systems guidebook notes that induction motor power factor runs from about 10 percent at no load to 85 percent or more at full load, which is a wider swing than most people expect.

LoadPower factor to expectWhy
Resistance heat, incandescent lamps1.0Current and voltage stay in step
Induction motor, near full load0.85 and upNameplate figure, best at rated load
Induction motor, light load0.10 to 0.50Magnetizing current dominates when unloaded
Oversized motor on a small jobFalls with the loadThe classic cause of a low plant power factor
Electronic supplies with power factor correction0.95 to 1.0The correction circuit is built in
Older UPS output stage0.8Printed on the nameplate, not a guess

When the exact figure matters, read it off the nameplate or ask the supplier for the test report. When it does not, use 0.8 for a mixed motor load and 1.0 for heat, and label the result as an estimate.

Why demand is billed in kVA

Residential bills are in kilowatt hours, which is energy: kW multiplied by hours. A commercial demand charge is different, and many tariffs measure it in kVA because the utility has to deliver the current whether or not it does work. The California Energy Commission's note on demand components puts it plainly: at a power factor of 0.8 the demand for a given kW rises by 25 percent, and at 0.5 it doubles.

That turns power factor into a line item. Take 250 kW of load at 0.92, which is 271.74 kVA, and correct it to 0.98, which is 255.10 kVA. The gap is 16.64 kVA, and at a demand charge of 12 dollars per kVA that is 199.65 dollars a month for current that never did any work.

Many utilities also add a penalty once the power factor drops below a threshold, and the Department of Energy's motor system guidance notes that a 95 percent threshold is common, so the practical target is 0.95 or better. Capacitors at the motor or the panel fix it, and the kVA to kW conversion on this page is how you measure whether the fix paid off.

Frequently asked questions

How many kW is 100 kVA?

It depends on the power factor. At 0.8 it is 80 kW, at 0.9 it is 90 kW, and at 1.0 it is 100 kW. kVA is apparent power and kW is real power, so the two are equal only at a power factor of 1.

What is the formula for kVA to kW?

kW = kVA x power factor for a single phase load. For three phase, kW = 1.732 x kVA x power factor, where the kVA figure is already the total for all three phases.

How many kW is 500 kVA?

500 kVA at a power factor of 0.9 is 450 kW. At 0.8 it is 400 kW, which is the difference between a UPS that can carry a modern server room and one that cannot.

How do I convert kVA to amps?

Single phase: amps = kVA x 1000 / volts. Three phase: amps = kVA x 1000 / (1.732 x volts). A 75 kVA load at 480 V three phase draws 90.21 amps.

Why is kVA always bigger than kW?

Because the power factor is at most 1. kW = kVA x power factor, so kW can only be equal to kVA or smaller. The gap is reactive power, measured in kVAR.

How many kW is 45 kVA at 0.8 power factor?

45 x 0.8 = 36 kW of real power, with 27 kVAR circulating. That leaves 36 kW of useful capacity from a unit rated at 45 kVA.

What is a good power factor?

0.95 or higher. Many utilities charge a penalty below that level, and the Department of Energy notes that a 95 percent threshold is common, so correction equipment usually aims for 0.95 to 0.98.

How many kVA do I need for a 250 kW load?

250 / 0.92 = 271.74 kVA at a power factor of 0.92, or 250 / 0.8 = 312.5 kVA at 0.8. Always size from the real load and the actual power factor, then round up to the next standard size.

Does the 1.732 apply to kW as well as amps?

Only once. If the kVA number is the three phase total, real power is kVA x power factor and the 1.732 is already inside. The factor appears again only when you convert between kVA and line current.

Is kVA the same as kWh?

No. kVA is a rate of apparent power at one instant, and kWh is energy over time. A 10 kVA load running for 2 hours uses at most 20 kWh, and exactly 20 kWh at a power factor of 1.0.

Why does my generator trip when the load is below its kW rating?

Because the generator is limited by current as well as by kW. At a power factor of 0.7 a 100 kVA set delivers 70 kW, and the alternator reaches its current limit before the engine reaches its rated output.

How many amps is 15 kVA at 208 V three phase?

15,000 / (1.732 x 208) = 41.64 amps per line. At 480 V the same 15 kVA draws 18.04 amps, which is why higher distribution voltages use smaller conductors.

Can a power factor be above 1?

No. Power factor is real power divided by apparent power, and real power can never exceed apparent power, so the value sits between 0 and 1. A reading above 1 means the meter or the capacitor bank is miswired.