VA to kW Calculator
Power factor decides how much of your VA turns into real kilowatts. A 1500 VA load at a power factor of 0.9 draws 1350 W, which is 1.35 kW. At a power factor of 1.0 the same load reaches 1.5 kW, so the factor you assume moves the answer by double digits.
Typical power factors: heaters near 1.0, mixed household or office loads near 0.9, motors near 0.8. If the equipment label prints a watt rating, use it. All calculations run in your browser, no data is uploaded.
Type in a VA rating and a power factor, and get real power in watts and kilowatts, plus the amps at your voltage.
Key takeaways
- The whole conversion is kW = VA x PF / 1000; nothing else in the formula changes the answer
- VA is apparent power, what the wiring and the breaker must carry; kW is the part that does work
- A 1500 VA load at PF 0.9 is 1.35 kW; at PF 0.8 it is 1.2 kW and at unity it is 1.5 kW
- Resistive loads like heaters run near PF 1.0; motor loads sit near 0.8; electronics with power factor correction run 0.9 to 0.99
- Current comes from the same VA number: amps = VA / volts, so 1500 VA is 12.5 A at 120 V and 6.25 A at 240 V
On this page
VA and kW measure two different things
Every AC load draws two kinds of power at once. Apparent power, measured in volt-amps (VA), is the full product of voltage and current, and it decides how much current flows through the wire, the breaker and the transformer upstream. Real power, measured in watts (W) or kilowatts (kW), is the part that turns into motion, light or heat and shows up on your electric bill. The ratio between them is the power factor, a number between 0 and 1.
The US Department of Energy motor systems guide draws it as a horse pulling a rail car at an angle: the horse's total effort is the apparent power, the pull along the track is the real power, and the wasted sideways pull is reactive power. The cos of the angle is the power factor. In their worked triangle, 100 kW of real power drawn from a 142 kVA supply is a power factor of 100 / 142 = 0.70, meaning only 70 percent of the current produces useful work.
That triangle comes straight from the DOE Fundamentals Handbook on electrical science, which defines apparent power S in volt-amperes, true power P in watts, and power factor as P / S = cos of the phase angle. Nothing about the definition depends on the size of the load, so the same math converts a 1500 VA desk setup and a 6000 VA machine the same way.
That split is why a nameplate can print one number and hide the other. A device stamped 500 VA tells you how much current it will pull and how big a breaker it needs, but says nothing about how much work it does. The same 500 VA can be a 500 W heater or a 400 W motor, and the label looks identical either way. Once you know the load type, the conversion fills in the missing half.
Two wrinkles show up on real equipment. Inverter and rectifier front ends distort the current waveform, so the plain cosine rule only approximates their factor, and a lagging induction motor looks different from a leading capacitor bank on a power quality analyzer. Neither wrinkle changes the arithmetic on this page; both change which factor you should type in.
The formula: kW = VA x PF / 1000
One line does the whole job:
kW = VA x PF / 1000
Divide by 1000 because VA lands in watts and kilowatts are thousands of watts. The only judgment call is PF, the power factor, and it is an assumption about the load, not a property of the VA number. The table shows the same six VA ratings converted at three common factors:
| VA | kW at PF 0.8 | kW at PF 0.9 | kW at PF 1.0 |
|---|---|---|---|
| 500 VA | 0.4 kW | 0.45 kW | 0.5 kW |
| 1000 VA | 0.8 kW | 0.9 kW | 1.0 kW |
| 1500 VA | 1.2 kW | 1.35 kW | 1.5 kW |
| 3000 VA | 2.4 kW | 2.7 kW | 3.0 kW |
| 5000 VA | 4.0 kW | 4.5 kW | 5.0 kW |
| 10000 VA | 8.0 kW | 9.0 kW | 10.0 kW |
The spread between the 0.8 and 1.0 columns is 25 percent at every row, because 1.0 / 0.8 = 1.25. That spread is the cost of not knowing your power factor. Pick a factor that matches the load, run the number, and you have kilowatts you can put against a breaker, a UPS watt rating or a bill.
Unit names shift with size but the math does not. A kilovolt-ampere is 1000 VA, so a 5 kVA transformer is 5000 VA, and 5000 x 0.9 / 1000 = 4.5 kW. Watts scale the same way into kilowatts. Whatever prefix the label uses, convert it to plain VA and watts first, then apply the power factor once, at the end. Doing it twice is the most common way to land a factor of a thousand off.
Worked example: a 1500 VA desk setup
Take a workstation that draws 1500 VA, with a power supply and monitor mix that puts the power factor at 0.9. The chain runs like this:
- Input: 1500 VA, PF 0.9
- Real power in watts: 1500 x 0.9 = 1350 W
- Real power in kilowatts: 1350 / 1000 = 1.35 kW
- Reactive power: 1500 x 0.436 = about 654 VAR
Run the same 1500 VA through a motor-heavy factor of 0.8 and the answer drops to 1.2 kW. Run it through a heater at unity and it climbs to 1.5 kW. The VA never moved; the assumption did all the work, which is exactly why every honest conversion states its power factor out loud.
On a real install the nameplate and the meter rarely agree. A supply stamped 1500 VA might pull 900 VA at idle and 1400 VA under load, and the power factor drifts with the load too, from roughly 0.7 at idle toward 0.95 at full tilt. A single conversion is a snapshot, so clamp the feed, read volts and amps, multiply, and use the factor the meter shows at the duty point you care about.
Worked example: a 6000 VA machine on a 240 V circuit
Now a shop machine stamped 6000 VA, running on a 240 V circuit, with an induction motor that pulls the power factor down to 0.8:
- Input: 6000 VA, PF 0.8, 240 V
- Real power: 6000 x 0.8 = 4800 W = 4.8 kW
- Current: 6000 / 240 = 25 A
- If the machine had PF 0.95 electronics instead: 6000 x 0.95 = 5700 W = 5.7 kW
Both versions draw the same 25 A and heat the same wire, but one delivers 4.8 kW of work and the other 5.7 kW. This is the whole reason supply equipment is rated in VA: the copper does not care about the split, only the total. Going the other way, a 4.8 kW load at PF 0.8 needs 4.8 x 1000 / 0.8 = 6000 VA of supply capacity.
What power factor should you assume?
The right factor depends on what is plugged in. These ranges cover common household and shop equipment for rough planning; a nameplate or a clamp meter beats any table:
| Load type | Typical power factor | Example |
|---|---|---|
| Resistive heating | about 1.0 | space heater, kettle, toaster, incandescent bulbs |
| Electronics with power factor correction | 0.95 to 0.99 | modern PC power supplies, laptop chargers |
| Mixed household or office load | 0.9 to 0.95 | computers, TVs, lights together on one circuit |
| Induction motors at full load | about 0.8 | fridge and freezer compressors, shop machines, pumps |
| Small or lightly loaded motors | 0.5 to 0.7 | idle machinery, small fans on light duty |
If the label prints both a VA and a watt number, skip the guessing entirely and divide: a unit marked 1500 VA / 900 W has a built-in factor of 0.6 at its rating point. The NIST Special Publication 811 keeps the units themselves straight (the volt-ampere for apparent power, the watt for real power), but the factor between them is always a property of the load in front of you.
When you have a meter, skip the table. A plug-in power meter shows watts directly, and if you also know the VA from the label, dividing gives the factor: a device reading 90 W on a 100 VA rating runs at 0.9. A clamp meter plus a voltage reading gets you the same place the other way around, since VA = volts x amps. Both beat guessing, and both take about a minute.
From VA to amps, and where phase fits
Current needs no power factor at all, because VA already is volts times amps. Rearranged: amps = VA / volts for a single phase circuit.
| VA | Amps at 120 V | Amps at 240 V |
|---|---|---|
| 500 VA | 4.17 A | 2.08 A |
| 1500 VA | 12.5 A | 6.25 A |
| 3000 VA | 25.0 A | 12.5 A |
| 5000 VA | 41.7 A | 20.8 A |
Those amp numbers explain why a 1500 VA load is the practical ceiling for one 15 A, 120 V branch: 12.5 A is 83 percent of the rating, right at the continuous-load limit. On a three phase supply the same VA comes out of three wires, and the per-line current is VA / (volts x 1.732), so a 10000 VA load at 208 V three phase draws 10000 / (208 x 1.732) = 27.8 A per line. Phase changes the arithmetic around VA, never the VA to kW conversion itself.
Breakers, conduit fill and wire ampacity all follow amps, so the VA figure is the one to hand an electrician. A 20 A circuit at 120 V carries 2400 VA, and many electricians keep a continuous load at 80 percent of that, which is 1920 VA. A 2000 VA welder or a big inverter charger sits right at the edge, and the kilowatt rating printed on the same box tells you nothing about whether the breaker holds.
Mistakes that make the answer wrong
- Assuming unity power factor across the board. That overstates real power for motors and electronics. A 3000 VA motor load at PF 0.8 delivers 2.4 kW, not 3, a 20 percent error before anything else goes wrong.
- Taking a UPS watt figure as a conversion. The 1500 VA / 900 W pair on a label is two ratings, not two units of one quantity; the 900 W already includes the maker's factor of 0.6.
- Dropping the 1000. VA times PF yields watts. A 6000 VA machine at PF 0.8 is 4800 W, which is 4.8 kW. Reporting 4800 kW off by a thousand happens more often than you would think on spec sheets.
- Sliding between kVA and VA. 5 kVA is 5000 VA. The kVA pages on this site cover the bigger units; this page keeps VA so the figures stay in household range.
- Expecting the current to shrink. Raising power factor buys kilowatts per amp, but amps at a given VA stay put, since amps = VA / volts regardless of the factor.
A panel schedule is where all of this lands. A subpanel with a 100 A main at 240 V has 24,000 VA of capacity; fill it with motor loads at 0.8 and it serves 19.2 kW, while resistance heat would use the full 24 kW. Same copper, same breaker, different work done.
Frequently asked questions
How do you convert VA to kW?
Multiply VA by the power factor, then divide by 1000. In symbols: kW = VA x PF / 1000. A 1000 VA load at a power factor of 0.9 works out to 1000 x 0.9 / 1000 = 0.9 kW. The power factor is the share of the current that turns into real work, and it has to be assumed or measured, because the VA label alone does not tell you what the load is.
How many kW is 1500 VA?
It depends on the power factor. At 0.8 the answer is 1.2 kW, at 0.9 it is 1.35 kW, and at a perfect 1.0 it is 1.5 kW. For a mixed household or office load, 0.9 is a reasonable planning number. If the label on the equipment prints a watt rating, use that number instead of assuming anything.
Is VA the same as watts?
No. VA is apparent power, the product of volts and amps, and it sizes the wiring, the breaker and the transformer. Watts are real power, the part that does actual work or becomes heat. They are equal only when the power factor is 1.0, which happens with purely resistive loads like a space heater or a kettle. Anything with a motor, a transformer or a switch-mode supply draws some current that does no work, so watts land below VA.
What power factor should I assume for a computer or office load?
Modern computer power supplies with active power factor correction draw at 0.95 to 0.99, so 0.95 is a fair planning value for a desk full of computers. Monitors, printers and small electronics run a bit lower. Mixed office loads usually land near 0.9, which is the default this calculator starts from. Old uncorrected supplies could sit near 0.6 to 0.7.
Why does my UPS say 1500 VA and 900 W?
The manufacturer has already applied its own output power factor: 900 / 1500 = 0.6. That label pair is not a conversion problem for you to solve; it is two separate ratings for the same box. The unit can pass 1500 VA of current-limited load or 900 W of real work, whichever limit hits first. So for sizing, read the watt number for real loads and the VA number for current-limited ones, and never assume a 1500 VA UPS delivers 1350 W unless its label says so.
How many amps is 1500 VA?
Divide VA by volts. At 120 V, 1500 / 120 = 12.5 A, which fits a standard 15 A circuit with a little headroom. At 240 V the same 1500 VA is 6.25 A. Notice that VA already contains the voltage, so this conversion never needs the power factor; the current the wire carries depends on apparent power, not on real power.
Can kW ever be higher than VA?
No. Power factor tops out at 1.0, so real power can approach apparent power but never pass it. A 2000 VA supply delivers at most 2 kW, and only into a purely resistive load. If some source claims more kW than VA, one of the two numbers is wrong, or the two numbers describe different pieces of equipment.
What is reactive power, and where does the missing power go?
The gap between VA and W is reactive power, measured in VAR. It sloshes back and forth between the source and the load each cycle while doing no work. For a 1500 VA load at PF 0.9, reactive power is 1500 x 0.436 = about 654 VAR, because sin(arccos 0.9) = 0.436. It still heats the wiring, which is why utilities care about it even though your meter may not.
Why are transformers and generators rated in VA or kVA instead of kW?
Heat in the copper windings follows the current, and current follows VA, not kW. A transformer has no idea what power factor its load will have, so the maker rates it in VA, the one number that is true regardless. The kilowatts it can deliver depend on your load: a 10 kVA transformer feeding motors at PF 0.8 delivers 8 kW, and the same unit feeding heaters delivers the full 10 kW.
What power factor do electric motors use?
Induction motors run near 0.8 at full load, and the factor drops as the load drops, sometimes into the 0.5 range at part load. That is why a shop full of motors has a much lower power factor than a house full of electronics. Big motors carry a nameplate with the rated power factor on it; small ones force you to plan around the usual 0.8 figure.
How do I convert kW back to VA?
Run the formula backwards: VA = kW x 1000 / PF. A 4.8 kW load at PF 0.8 needs 4.8 x 1000 / 0.8 = 6000 VA of supply. At PF 0.95 the same load needs only 5053 VA. That is why improving power factor frees up capacity in a panel without touching the real load at all.
How many kW is 10000 VA?
At PF 0.9 it is 9 kW, at 0.8 it is 8 kW, and at unity it is 10 kW. A number like 10000 VA usually shows up on small transformers, subpanels or big UPS units, where the rating describes what the copper can carry. Multiply by the power factor of whatever you plug in, and the kilowatts follow.
Does the conversion change between single phase and three phase?
The VA to kW conversion itself does not: kW = VA x PF / 1000 either way. Phase only matters when you come in from voltage and current. Single phase uses VA = volts x amps, while three phase uses VA = volts x amps x 1.732. So a three phase load drawing 10 A at 208 V per line is 208 x 10 x 1.732 = 3603 VA, which is 3.24 kW at PF 0.9.
Does a low power factor cost money?
For most homes, no, because residential meters bill kilowatt-hours only. Many utilities bill larger commercial customers for demand in kVA or add power factor penalties, because low factor current still costs them wire heat and transformer capacity. That is why factories install capacitor banks: raising a plant from 0.8 toward 0.95 cuts the kVA the utility sees for the same kilowatts of production.
Spotted a wrong number or a broken result?
More Tech tools
- Amp-Hour Calculator
- Amps to kVA Calculator
- Audio File Size Calculator: WAV, MP3 and Storage Time
- Bandwidth Calculator
- Battery Charge Time Calculator
- Battery Life Calculator
- Bits to Bytes Converter
- CFM Calculator
- Capacitance
- Capacitor Calculator
- Current Calculator
- Data Transfer Calculator
- Data Usage Calculator
- Download Time Calculator
- Downtime Cost Calculator
- Electric Charge Calculator
Fee schedules, rates and rules change without notice. Always confirm important figures with the official source before you rely on them.