Voltage Drop Calculator
On a 120 volt, 20 amp circuit with 100 feet of 12 AWG copper, the drop is 7.72 volts. That is 6.43 percent of the supply, well over the 3 percent design target, while 8 AWG brings the same run down to 3.06 volts and 2.55 percent.
| Voltage drop | |
| Volts lost | |
| Voltage at the load | |
| One-way resistance | |
| Loop resistance | |
| Against the 3 percent target | |
| Smallest gauge that meets 3 percent |
Resistance values are from NEC Chapter 9 Table 8 for uncoated conductors at 75 C. The estimate ignores reactance, so treat long high-current feeders as a starting point. Everything runs in your browser, nothing is uploaded.
Enter the supply voltage, the load current, the one-way run length and the wire gauge to get the volts lost in the conductor, the percentage drop and the voltage that reaches the load.
Key takeaways
- Single phase drop = 2 x current x one-way resistance, so 2 x 20 x 0.193 = 7.72 volts
- Percent drop = volts lost / supply voltage, so 7.72 / 120 = 6.43 percent
- 12 AWG fails a 100 foot, 20 amp run; 10 AWG is 4.03 percent and 8 AWG is 2.55 percent
- The 3 percent branch circuit and 5 percent total figures are NEC informational notes, not code limits
On this page
What voltage drop is and why it matters
Every conductor has resistance, and current flowing through resistance loses voltage. The supply might be 120 volts at the panel, but the far end of a long run sees less, and the difference is voltage drop.
The effect is easy to underestimate. A 6 percent drop on a 120 volt circuit leaves 112.3 volts at the outlet, which most electronics tolerate. The same 6 percent on a 240 volt motor leaves 225.6 volts, and a motor that is designed for 230 volts will draw more current to produce the same torque, run hotter, and fail earlier. On a 12 volt lighting circuit, 6 percent is 0.72 volts and the lamps visibly dim toward the end of the run.
Two separate questions decide wire size, and they are often confused:
- Ampacity: can the conductor carry the current without overheating? This is a safety question and the tables in the electrical code answer it.
- Voltage drop: will the equipment at the far end receive enough voltage to work? This is a performance question, and it depends on length in a way ampacity does not.
A 20 amp circuit can be wired in 12 AWG and still deliver poor voltage at 200 feet. The wire is safe; the run is too long for the load.
The formula for single phase and three phase
The drop depends on current, conductor resistance and length. Resistance tables list ohms per 1,000 feet, so the length is divided by 1,000 before it is used.
Single phase: volts lost = 2 x current x (ohms per 1,000 ft x one-way feet / 1,000)
The 2 accounts for the return conductor. Current goes out on the hot leg and back on the neutral, so the loop is twice the one-way distance. Leaving the 2 out halves the answer and is the most common error in hand calculations.
Three phase: volts lost = 1.732 x current x (ohms per 1,000 ft x one-way feet / 1,000)
Three phase uses 1.732, the square root of 3, instead of 2. The factor comes from the way the three phases combine, and it assumes a balanced load. An unbalanced load needs a more careful calculation than this page does.
Percent drop = volts lost / supply voltage x 100. That last step matters because 7.72 volts is trivial on a 480 volt feeder and serious on a 120 volt branch circuit.
The other form of the same formula uses circular mils: volts lost = 2 x K x current x length / circular mils, with K around 12.9 for copper and 21.2 for aluminum. For the 12 AWG example that gives 7.90 volts against the 7.72 from the resistance table, about 2 percent higher, because K is a rounded constant rather than a table value.
Worked example: 20 amps on a 120 volt circuit
A workshop wants a 20 amp outlet 100 feet from the panel, wired in 12 AWG copper. The code table gives 12 AWG copper a resistance of 1.93 ohms per 1,000 feet at 75 degrees Celsius.
- One-way resistance: 1.93 x 100 / 1,000 = 0.193 ohms.
- Loop resistance: 2 x 0.193 = 0.386 ohms.
- Volts lost: 20 x 0.386 = 7.72 volts.
- Percent: 7.72 / 120 = 6.43 percent.
- Voltage at the outlet: 120 - 7.72 = 112.28 volts.
That is more than twice the 3 percent design target, so the next sizes are worth checking. Each step up in gauge cuts the resistance by about a third.
| Gauge | Ohms per 1,000 ft | Volts lost | Percent drop | Volts at load |
|---|---|---|---|---|
| 12 AWG | 1.93 | 7.72 | 6.43 | 112.28 |
| 10 AWG | 1.21 | 4.84 | 4.03 | 115.16 |
| 8 AWG | 0.764 | 3.06 | 2.55 | 116.94 |
| 6 AWG | 0.491 | 1.96 | 1.64 | 118.04 |
The 10 AWG step removes almost 3 volts and still misses the 3 percent target at 4.03 percent. Only 8 AWG gets under it, and 6 AWG leaves a comfortable margin. Copper prices climb fast at that size, which is why long runs often move the panel closer instead.
Worked example: a 240 volt tool and a three phase run
A 240 volt, 40 amp welder sits 150 feet from the panel, wired in 8 AWG copper. The resistance is 0.764 ohms per 1,000 feet.
- One-way resistance: 0.764 x 150 / 1,000 = 0.1146 ohms.
- Volts lost: 2 x 40 x 0.1146 = 9.17 volts.
- Percent: 9.17 / 240 = 3.82 percent.
That fails a 3 percent branch circuit target and passes the 5 percent total. Dropping to 6 AWG gives 0.491 x 150 / 1,000 = 0.0737 ohms, 2 x 40 x 0.0737 = 5.90 volts, and 5.90 / 240 = 2.46 percent. The higher supply voltage is doing most of the work here: the same 9.17 volts on a 120 volt circuit would be 7.6 percent.
Now a three phase case. A 208 volt, 30 amp motor load is 250 feet away on 8 AWG copper.
- One-way resistance: 0.764 x 250 / 1,000 = 0.191 ohms.
- Volts lost: 1.732 x 30 x 0.191 = 9.92 volts.
- Percent: 9.92 / 208 = 4.77 percent.
6 AWG gives 0.491 x 250 / 1,000 = 0.1228 ohms, then 1.732 x 30 x 0.1228 = 6.38 volts, which is 3.07 percent, still a hair over. 4 AWG lands at 4.00 volts and 1.92 percent. Three phase saves conductor compared with single phase at the same power, because the 1.732 factor replaces the 2 and each conductor carries less current for the same total watts.
Wire resistance by gauge
These values come from NEC Chapter 9 Table 8 for uncoated conductors at 75 degrees Celsius, the temperature the code uses for most circuit calculations. Resistance rises with temperature, so a conductor running hot has slightly more drop than the table predicts.
| Gauge | Copper, ohms per 1,000 ft | Aluminum, ohms per 1,000 ft | Aluminum vs copper |
|---|---|---|---|
| 14 AWG | 3.07 | not listed | not used |
| 12 AWG | 1.93 | 3.18 | 1.65 times higher |
| 10 AWG | 1.21 | 2.00 | 1.65 times higher |
| 8 AWG | 0.764 | 1.26 | 1.65 times higher |
| 6 AWG | 0.491 | 0.808 | 1.65 times higher |
| 4 AWG | 0.308 | 0.508 | 1.65 times higher |
| 2 AWG | 0.194 | 0.319 | 1.64 times higher |
Aluminum carries about 61 percent of the conductivity of copper for the same size, so the same gauge drops roughly 1.65 times as many volts. That is not a reason to avoid aluminum: it is lighter and cheaper for service entrance and feeder work, and it is widely used there. It is a reason to size aluminum two gauges larger when matching a copper design, and to use the aluminum column rather than the copper one.
An 8 AWG aluminum run of 100 feet at 20 amps on 120 volts gives 1.26 x 100 / 1,000 = 0.126 ohms, then 2 x 20 x 0.126 = 5.04 volts, which is 4.20 percent. The same run in 8 AWG copper is 2.55 percent, so the material choice alone changes the verdict.
Where the 3 percent and 5 percent numbers come from
The familiar targets are 3 percent on a branch circuit and 5 percent for the feeder plus branch combined. They are recommendations in informational notes to the National Electrical Code, at 210.19(A) for branch circuits and 215.2(A) for feeders, not enforceable rules. The NFPA 70 page is the place to confirm the current edition and the exact wording.
Informational notes are explanatory text. Section 90.5 of the code says as much, which means an inspector cannot fail an installation for a 4 percent drop on the basis of that note alone. What can bind you is a local amendment, a project specification, or the listing instructions of the equipment, and some jurisdictions do adopt the 3 percent figure as a rule.
| Segment | Common design target | Status in the NEC |
|---|---|---|
| Branch circuit to the farthest outlet | 3 percent | Informational note, 210.19(A) |
| Feeder | Counts toward the total | Informational note, 215.2(A) |
| Feeder plus branch | 5 percent | Informational note |
| Ampacity and overcurrent protection | Table values | Enforceable requirements |
The 5 percent budget is shared, not stacked. If the feeder eats 2 percent, the branch circuit has 3 percent left. Designers often give the feeder 1 to 2 percent and leave the rest for the branch, which is why a long service run can force larger conductors even when the branch circuit is short.
OSHA's electrical wiring rules in 29 CFR 1910 Subpart S cover conductor sizing and overcurrent protection for workplaces, and they point back to the same code framework rather than setting a separate voltage drop number.
Low voltage runs and other mistakes
The lower the supply voltage, the more a given number of lost volts matters. A 12 volt landscape lighting run of 50 feet at 5 amps on 12 AWG copper shows why.
- One-way resistance: 1.93 x 50 / 1,000 = 0.0965 ohms.
- Volts lost: 2 x 5 x 0.0965 = 0.965 volts.
- Percent: 0.965 / 12 = 8.04 percent.
8 AWG brings it to 0.38 volts and 3.18 percent, and 6 AWG to 0.25 volts and 2.05 percent. The usual fix on landscape lighting is not bigger wire but a transformer tap one step higher, or shorter runs with fewer fixtures on each.
| Mistake | What it does to the answer | Fix |
|---|---|---|
| Using the one-way length | Halves the drop | Double the length, or use the 2 in the formula |
| Using the breaker rating as the load | Overstates the drop | Use the actual running current, not the trip point |
| Reading the copper column for aluminum | Understates the drop by about 40 percent | Use the aluminum resistance |
| Forgetting the 1.732 on three phase | Overstates the drop by about 15 percent | Use 1.732 instead of 2 |
| Sizing on voltage drop alone | Can leave a conductor undersized for current | Check ampacity first, then voltage drop |
One more: a load that cycles, such as a compressor or a welder, draws a starting current several times its running current. The drop during that inrush is brief, but it can trip a contactor or dim every light on the circuit. Sizing the run for the running current and then checking the start is the practical order.
This page estimates drop from resistance alone and ignores reactance, which matters on large feeders and on long runs at high current. For a service entrance or a feeder over roughly 100 amps, use the full calculation from the code rather than this estimate.
Frequently asked questions
How do you calculate voltage drop?
Multiply the current by the conductor resistance for the full loop. For single phase, drop = 2 x current x (ohms per 1,000 ft x length / 1,000). A 20 amp load on 100 feet of 12 AWG copper gives 2 x 20 x 0.193 = 7.72 volts.
What is the voltage drop on 100 feet of 12 AWG at 20 amps?
7.72 volts on a 120 volt circuit, which is 6.43 percent. The load sees 112.28 volts, well past the 3 percent design target.
What gauge wire do I need for a 100 foot 20 amp run?
8 AWG copper keeps the drop at 2.55 percent on 120 volts. 10 AWG gives 4.03 percent and 12 AWG gives 6.43 percent, so both miss the 3 percent target.
Is 3 percent voltage drop required by code?
Not by the National Electrical Code itself. The 3 percent branch circuit and 5 percent total figures appear in informational notes at 210.19(A) and 215.2(A), which are recommendations. Local amendments and project specs can make them mandatory.
Why is there a 2 in the single phase formula?
Because current travels out on one conductor and back on another, so the path is twice the one-way distance. For 100 feet of 12 AWG the loop resistance is 2 x 0.193 = 0.386 ohms.
Why does three phase use 1.732 instead of 2?
The three phases share the return path, and the vector sum of the currents is the square root of 3 times the per-phase value. A 208 volt, 30 amp load 250 feet out on 8 AWG copper drops 9.92 volts, or 4.77 percent.
How much does aluminum wire drop compared with copper?
About 1.65 times as much for the same gauge, because aluminum has roughly 61 percent of copper's conductivity. An 8 AWG aluminum run of 100 feet at 20 amps drops 5.04 volts, or 4.20 percent, against 2.55 percent for copper.
What is a normal voltage drop for a 120 volt circuit?
Aim for 3 percent or less, which is 3.6 volts on 120 volts. The load then sees at least 116.4 volts, and most equipment is happy.
Does voltage drop affect a 12 volt lighting run more?
Yes, because the percentage is the lost volts divided by a small supply. A 50 foot, 5 amp run on 12 AWG loses 0.965 volts, which is 8.04 percent of 12 volts but only 0.8 percent of 120 volts.
Can I just use a bigger breaker instead of bigger wire?
No. The breaker protects the conductor from overheating, and a larger breaker on the same wire makes the installation less safe. Voltage drop is fixed by conductor size, length or supply voltage.
Should I use the running current or the breaker size?
Use the current the equipment draws. A 20 amp breaker on a tool that pulls 12 amps should be calculated at 12 amps, which cuts the drop from 7.72 to 4.63 volts on the same 100 foot run.
What is the total voltage drop allowed from the meter to the outlet?
The common design target is 5 percent for the feeder plus the branch circuit combined, with no more than 3 percent on either one. On a 120 volt supply that is 6 volts in total.
Does temperature change the resistance?
Yes. The table values are at 75 degrees Celsius, and copper resistance rises about 0.4 percent per degree Celsius above that. A conductor running cooler has slightly less drop than the table shows.
What does the load voltage figure mean?
It is the supply voltage minus the volts lost in the conductor. On the 120 volt example the load sees 112.28 volts, and that is the number the equipment runs on.
Spotted a wrong number or a broken result?
More Tech tools
- Amp-Hour Calculator
- Amps to kVA Calculator
- Audio File Size Calculator: WAV, MP3 and Storage Time
- Bandwidth Calculator
- Battery Charge Time Calculator
- Battery Life Calculator
- Bits to Bytes Converter
- CFM Calculator
- Capacitance
- Capacitor Calculator
- Current Calculator
- Data Transfer Calculator
- Data Usage Calculator
- Download Time Calculator
- Downtime Cost Calculator
- Electric Charge Calculator
Fee schedules, rates and rules change without notice. Always confirm important figures with the official source before you rely on them.