kVA to VA Calculator
One kVA is 1,000 volt-amps, so a 2.5 kVA load is 2,500 VA. The volts and the amps never change between the two labels: 2,500 VA at 120 volts draws 2,500 / 120 = 20.83 amps, and the same math runs a UPS, a transformer or a breaker sizing check.
| Apparent power | |
| Same power in kVA | |
| Real power at your power factor | |
| Line current | |
kVA is 1,000 VA, watts are VA times the power factor, and amps are VA divided by volts. Three phase current uses 1.732 x volts. All calculations run in your browser, and nothing you type is uploaded or stored.
Type a kVA or VA figure plus your voltage and get the matching value, the amps behind it, and the watts it can deliver at a chosen power factor.
Key takeaways
- VA = volts x amps, and kVA = VA / 1,000, so 2.5 kVA = 2,500 VA
- 2,500 VA at 120 V is 20.83 amps, and the same VA at 240 V is 10.42 amps
- A 30 A, 120 V circuit carries 30 x 120 = 3,600 VA
- A 1,500 VA UPS with a 900 W limit serves a 900 W load at 0.6 power factor at exactly 1,500 VA
On this page
A volt-amp and a watt are not the same thing
Volt-amps measure what a circuit carries, and watts measure what the load does with it. A volt-amp is one volt times one amp, the raw product of the two quantities at an instant. A watt is that same product after the current's phase angle is counted: watts = VA x power factor. A space heater with a resistive element runs near a power factor of 1.0, so its VA and watt ratings match. A motor, a compressor or an older computer supply runs lower, and the gap is current the utility still has to deliver.
The gap widens with the type of load. The Department of Energy's motor systems guidebook puts an induction motor's power factor near 0.1 at no load and at 0.85 or better at full load, which is why a lightly loaded motor drags a building's numbers down while a resistive heater never does.
The difference between VA and kVA is the metric prefix kilo, which means 1,000. That is the whole relationship: 1 kVA is 1,000 VA, 2.4 kVA is 2,400 VA, and 0.6 kVA is 600 VA. Nothing about the load, the voltage or the power factor changes, because the two labels describe the same current through the same wires.
Why keep two words for one quantity? Because equipment makers quote the number their product is limited by. A UPS is limited by the current its inverter can pass, which is a VA figure. A generator is limited by the watts its engine can turn, which is a watt figure. Reading both labels off a nameplate is the fastest way to see where a device runs out of capacity.
The conversion is a thousand, not a formula
Because a kilo is 1,000, converting between the two units means moving the decimal point three places. No division by voltage, no multiplication by a power factor, no square root of three. The table below is the entire method.
| Direction | Rule | Example |
|---|---|---|
| kVA to VA | multiply by 1,000 | 2.5 kVA becomes 2,500 VA |
| VA to kVA | divide by 1,000 | 600 VA becomes 0.6 kVA |
| kVA to watts | multiply by 1,000, then by the power factor | 2.5 kVA at 0.8 becomes 2,000 W |
The one conversion in this family that does need a formula is the step to real power. Multiply the kVA by 1,000 and then by the power factor. A 2.5 kVA supply at a power factor of 0.8 delivers 2,000 W, and the same supply at 0.9 delivers 2,250 W. The kVA to kW calculator covers that direction in detail, including the three phase version where the square root of three appears once and only once.
How many amps is that kVA? The voltage step
Amps are where kVA meets the building, because breakers, wires and fuses are sized in amps. For a single phase circuit, amps = VA / volts. A 4,800 VA load on 120 volts pulls 4,800 / 120 = 40 amps, and the same load on 240 volts pulls 4,800 / 240 = 20 amps.
The table below turns common kVA ratings into amps at the three voltages that show up in North American buildings.
| Rating | At 120 V | At 240 V | At 277 V |
|---|---|---|---|
| 0.6 kVA (600 VA) | 5.00 A | 2.50 A | 2.17 A |
| 1.5 kVA (1,500 VA) | 12.50 A | 6.25 A | 5.42 A |
| 2.4 kVA (2,400 VA) | 20.00 A | 10.00 A | 8.66 A |
| 3.6 kVA (3,600 VA) | 30.00 A | 15.00 A | 13.00 A |
| 4.8 kVA (4,800 VA) | 40.00 A | 20.00 A | 17.33 A |
| 7.2 kVA (7,200 VA) | 60.00 A | 30.00 A | 25.99 A |
Three phase loads use a different divisor: amps = VA / (1.732 x line to line volts). A 10 kVA load on a 208 volt three phase panel draws 10,000 / (1.732 x 208) = 27.76 amps per line. The 1.732 is the square root of three, and it belongs in the amps step only. Applying it to the kVA to VA conversion would inflate the apparent power by 73 percent for no reason.
Breakers count amps, panels count VA
The same 20 amp breaker carries 2,400 VA at 120 volts and 4,800 VA at 240 volts, because VA is volts times amps and the voltage doubled while the current stayed put. That is why a dryer or a range gets a 240 volt circuit with modest amps and large apparent power, and why a panel schedule lists both numbers.
Continuous loads follow an 80 percent rule in North American practice: a breaker is loaded to at most 80 percent of its rating for anything that runs three hours or more. A 20 amp, 120 volt circuit therefore supplies 1,920 VA of continuous load, not 2,400 VA. A 1,500 W heater draws 12.5 amps, which is why it needs a 20 amp circuit if anything else shares it.
| Circuit | VA at full rating | Continuous load at 80 percent |
|---|---|---|
| 15 A, 120 V | 1,800 | 1,440 |
| 20 A, 120 V | 2,400 | 1,920 |
| 20 A, 240 V | 4,800 | 3,840 |
| 30 A, 240 V | 7,200 | 5,760 |
| 50 A, 240 V | 12,000 | 9,600 |
Read the table backwards when a load list gives you VA instead of amps. A 3,600 VA load fits a 20 amp, 240 volt circuit with room to spare, and the same load would sit exactly at the limit of a 30 amp, 120 volt circuit with nothing else on it.
From kVA to watts: the power factor step
Apparent power becomes real power when you multiply by the power factor, the number that says how much of the current is in step with the voltage. A 2.5 kVA transformer loaded to a power factor of 0.8 delivers 2.0 kW of real power, and at 0.9 it delivers 2.25 kW. The difference is not heat in the transformer. It is current that shuttles back and forth without doing work, and the utility sizes its equipment for it all the same.
| Power factor | Real power from 2.5 kVA |
|---|---|
| 1.0 | 2,500 W |
| 0.9 | 2,250 W |
| 0.8 | 2,000 W |
| 0.7 | 1,750 W |
| 0.5 | 1,250 W |
Working backwards, a load list in watts becomes a kVA figure by division. A rack that draws 1,800 W at a power factor of 0.9 needs 1,800 / 0.9 = 2,000 VA, or 2 kVA. Add headroom for growth and for the power factor of future gear before buying: a unit sized exactly at 2 kVA runs near its limit on day one, and a laser printer on the same circuit can push it over.
Reading the two numbers on a UPS label
A UPS nameplate carries both numbers for a reason. The inverter and its wiring are limited by current, which is the VA figure, and the electronics and battery are limited by watts. A 1,500 VA unit with a 900 W limit has an output power factor of 0.6: a load that draws 900 W at 0.6 power factor fills the VA rating exactly, and the same 900 W at 0.95 power factor fills only 947 VA of it.
Modern equipment with active power factor correction runs at 0.95 or better, and the ENERGY STAR specification for uninterruptible power supplies tests at a reference load above 0.99 power factor (ENERGY STAR UPS Version 2.0). That is why newer labels sit closer to unity than the 0.6 units of twenty years ago, and why the watt number is the one that limits a modern server rack.
The practical check is a two column sum: add the watts of everything that must stay up, add the VA as well, and choose a unit where both totals fit with room to grow. A 300 W monitor at 0.95 power factor and a 200 W older supply at 0.7 come to 500 W and about 600 VA, so a 650 W, 1,000 VA unit fits both columns with headroom, while a 500 VA unit fails on apparent power before the watts even matter.
Where the conversion goes wrong
Three mistakes account for most of the confusion. The first is mixing kVA with kWh: kVA is a rate at an instant and kWh is energy over time, so a 2.4 kVA load at 0.8 power factor running 3 hours uses 2.4 x 0.8 x 3 = 5.76 kWh. The second is applying the power factor twice, once on the way from kVA to VA and again on the way to watts; the prefix step has no power factor in it at all. The third is adding the 1.732 factor to a three phase kVA figure that already counts all three phases, which inflates the answer by 73 percent.
A quieter error is rounding the prefix: 2.5 kVA is 2,500 VA, not 250 VA and not 25,000 VA. A misplaced zero is the most common reason a load looks fine on paper and trips a breaker in the room.
Run any of these through the calculator above. It converts in both directions, resolves the amps at the voltage you enter, and shows the watts the load can deliver at a chosen power factor, and nothing you type leaves the page. The electricity cost calculator takes the watt result the rest of the way to a bill.
Frequently asked questions
How many VA is 1 kVA?
Exactly 1,000. The k is the metric prefix for a thousand, so 1 kVA is 1,000 VA, 2.5 kVA is 2,500 VA and 10 kVA is 10,000 VA.
How do I convert VA to kVA?
Divide by 1,000: 2,400 VA is 2.4 kVA and 600 VA is 0.6 kVA. Going the other way multiplies by 1,000, so 1.5 kVA is 1,500 VA.
Is VA the same as watts?
No. VA counts volts times amps and watts counts the work done, with watts = VA x power factor. A 3,000 VA load at 0.7 power factor does 2,100 W of work.
How many amps is 1,500 VA at 120 volts?
12.5 amps, because 1,500 / 120 = 12.5. The same 1,500 VA at 240 volts draws 6.25 amps, which is why higher voltage circuits need smaller wire.
What size breaker do I need for 2,400 VA?
At 120 volts that is 20 amps, a standard breaker size. For a continuous load the 80 percent rule leaves 1,920 VA of usable capacity, so a 2,400 VA heater wants a larger circuit.
Why do UPS labels show both VA and watts?
The inverter passes current up to its VA rating, and the electronics and battery limit the watts. A 1,500 VA unit with a 900 W limit serves a 900 W load at 0.6 power factor at exactly 1,500 VA, and the same 900 W at 0.95 power factor needs only 947 VA.
How many kVA is a 100 amp panel?
At 240 volts single phase, 100 x 240 = 24,000 VA, or 24 kVA. A 100 amp service is normally described in amps, but the VA figure matters when you compare it with a generator or a transformer.
Does power factor change kVA to VA?
No. The prefix step is independent of power factor and applies to any load. The power factor enters when you go from VA to watts, and a 1,000 VA load at 0.8 delivers 800 W.
How many VA does a space heater use?
A 1,500 W space heater on a resistive element runs at a power factor of 1.0, so it draws 1,500 VA, or 1.5 kVA. Two of them on one 20 amp, 120 volt circuit exceed the 2,400 VA that circuit carries.
What is the difference between kVA and kWh?
kVA is apparent power at one instant and kWh is energy over time. A 2.4 kVA load at 0.8 power factor for 3 hours uses 2.4 x 0.8 x 3 = 5.76 kWh.
How do I convert kVA to amps in three phase?
Use amps = VA / (1.732 x line voltage). A 10 kVA load at 208 volts three phase draws 10,000 / (1.732 x 208) = 27.76 amps per line.
What does 100 VA mean on a device?
It means the device draws 100 volts times amps of apparent power. On a 120 volt circuit a 100 VA device pulls 0.83 amps at a power factor of 1.0, and slightly more current at a lower power factor.
Spotted a wrong number or a broken result?
More Tech tools
- Amp-Hour Calculator
- Amps to kVA Calculator
- Audio File Size Calculator: WAV, MP3 and Storage Time
- Bandwidth Calculator
- Battery Charge Time Calculator
- Battery Life Calculator
- Bits to Bytes Converter
- CFM Calculator
- Capacitance
- Capacitor Calculator
- Current Calculator
- Data Transfer Calculator
- Data Usage Calculator
- Download Time Calculator
- Downtime Cost Calculator
- Electric Charge Calculator
Fee schedules, rates and rules change without notice. Always confirm important figures with the official source before you rely on them.