kVA to Watts Calculator

One kVA at a power factor of 0.8 delivers 800 watts of real power. At unity the same kVA is 1,000 W, so the watts behind a kVA rating depend on the load.

Enter kVA and the power factor to get watts, or start from a watt rating and find the kVA behind it. The page covers the 1,000 factor, single and three phase current, and the nameplates you will meet.

By the Lelifi editors ·

Key takeaways

Watts of real power from a 10 kVA supplyPower factor 0.55,000 WPower factor 0.77,000 WPower factor 0.88,000 WPower factor 0.99,000 WPower factor 0.959,500 WPower factor 1.010,000 WThe kVA figure never changes. Only the power factor of the load moves the watt figure.
The same 10 kVA supply, six loads, six different watt figures.
Line current at 480 V, three phase25 kVA30.07 A50 kVA60.14 A75 kVA90.21 A100 kVA120.28 AFull load current for a three phase supply at 480 V, from 25 kVA to 100 kVA.
Full load line current at 480 V three phase for four common kVA ratings.
On this page
  1. What one kVA is worth in watts
  2. The formula in both directions
  3. Single phase current from watts
  4. Three phase: the 1.732 belongs to the current
  5. Nameplates: what a 1 kVA UPS gives you
  6. Why the load sets the power factor
  7. From watts to the electricity bill

What one kVA is worth in watts

kVA measures apparent power, the volts and amps that the wiring and the breaker have to carry. Watts measure real power, the part that turns a motor or heats a room. One multiplication links them: watts = kVA x 1,000 x power factor.

At a power factor of 1.0 the two numbers line up, and 1 kVA is exactly 1,000 W. Resistive loads behave that way: kettles, storage heaters, incandescent lamps. Almost everything else pulls current out of step with the voltage, so the watt figure lands below the kVA figure. A 1 kVA supply feeding a 0.8 load delivers 800 W, and the remaining 600 VAR circulates between the load and the source without doing work.

The watt is a derived SI unit, one joule per second, and the NIST list of SI derived units sets out its definition. kVA has no separate entry because a volt-ampere is already a watt in units, which is exactly why the power factor has to be applied to turn one into the other.

Power factorWatts from 1 kVAWatts from 10 kVAkVAR at 10 kVA
1.01,00010,0000
0.99009,0004.36
0.88008,0006.00
0.77007,0007.14
0.55005,0008.66

The formula in both directions

From kVA to watts, multiply by 1,000 and then by the power factor. From watts to kVA, divide by 1,000 and then by the power factor. Both directions earn their place. A load schedule lists watts because that is what the equipment consumes, and the purchase order is written in kVA because that is how transformers, generators and UPS units are sold.

A 1,200 W motor load at a power factor of 0.75 needs 1,200 / (1,000 x 0.75) = 1.6 kVA. A 2 kVA unit covers it with room to spare, while a 1.5 kVA unit is already over its current limit. Running the other way, 2.4 kVA at 0.9 gives 2,400 x 0.9 = 2,160 W, so a 2.4 kVA label is a 2.16 kW promise.

Two slips show up again and again. Dropping the 1,000 returns kilowatts instead of watts, a factor of a thousand out. Treating kVA as watts assumes a power factor of 1.0, which overstates the usable output of every motor load on the list.

LoadWattsPower factorkVA needed
Workshop motor1,2000.751.60
Storage heater1,5001.01.50
UPS load2,1600.92.40
Mixed office load8000.81.00
Arc welder5,0000.77.14

Nameplate arithmetic is the other place this conversion earns its keep. A motor nameplate lists output watts, efficiency and power factor as separate numbers, so the input kVA is the output divided by efficiency and then by the power factor. A 1,500 W motor at 88 percent efficiency and 0.82 power factor draws 1,500 / 0.88 = 1,705 W from the line, and that load needs 1,705 / 0.82 = 2,079 VA of supply.

Single phase current from watts

Once watts are known, current follows from the voltage: amps = watts / (volts x power factor). An 8,000 W load on 240 V at 0.9 draws 8,000 / 216 = 37.04 A. The same 8,000 W at 120 V would draw 74.07 A, which is why high draw appliances in North America move up to 240 V.

Resistive appliances are the easy case. A 1,500 W kettle at 120 V draws 12.5 A, and a 3,500 W water heater at 240 V draws 14.58 A. Electronics are less tidy: a 900 W load at 0.9 needs 8.33 A at 120 V, and a 900 W load at 0.7 needs 10.71 A. The breaker is sized for the current, not for the watt figure.

Rounding the other way hides a problem. A 2,000 W load at 230 V and 0.95 draws 9.15 A, which sits under a 10 A breaker, but the same load at 0.8 draws 10.87 A and trips that breaker on a warm afternoon. The watts did not change. The current did.

ApplianceWattsVoltsPower factorAmps
Kettle1,5001201.012.50
Hair dryer1,8001201.015.00
Water heater3,5002401.014.58
UPS load9001200.98.33
Workshop motor2,0002300.959.15

A long extension lead makes the same point from the other side. The resistance of the cable drops volts along its length, so a 2,000 W appliance at the far end runs below its rated voltage. A resistive heater delivers less heat and draws less current, while a motor or a switch mode supply draws more current to hold its output, and that extra current adds to the drop. Keep high draw loads on a short, thick lead and the calculation above stays honest.

Three phase: the 1.732 belongs to the current

A three phase kVA rating already counts all three phases, so the watts follow the same rule as single phase: watts = kVA x 1,000 x power factor. The square root of three enters only when line current is involved, amps = watts / (1.732 x volts x power factor), with volts measured line to line.

80,000 W at 480 V and 0.8 pulls 80,000 / (1.732 x 480 x 0.8) = 120.28 A per line. The same 80,000 W at 208 V pulls 277.6 A, which is why distribution runs at the higher voltage and steps down near the equipment.

Folding the factor in twice is the usual error. A 25 kVA three phase unit at 0.85 delivers 21,250 W, and multiplying that by 1.732 would inflate it by 73 percent. The 1.732 belongs to the amps calculation only, because the kVA figure is already a three phase total.

kVAPower factorWattsAmps at 480 V three phase
250.8521,25030.07
500.840,00060.14
750.967,50090.21
1000.880,000120.28

Balance matters as much as the formula. A three phase alternator or transformer feeding unequal single phase loads carries current in the neutral, and the kVA rating assumes the phases share the work evenly. A 100 kVA unit with one heavily loaded phase reaches its per-winding limit while the other two sit half idle, so the watts available in practice fall below the nameplate arithmetic. Switchgear, feeder cables and the breaker are sized from that same current, which is why balancing a panel schedule comes before adding load.

Nameplates: what a 1 kVA UPS gives you

Retail hardware is quoted in VA because that is what its components carry, and the watt figure that comes out depends on the output power factor in the spec sheet. A 1 kVA UPS rated at 0.9 gives 900 W. An older unit rated at 0.6 gives 600 W from the same 1 kVA label, and the difference is the inverter's current limit rather than a marketing choice.

Generators follow the same pattern. A 5 kVA portable set at 0.8 delivers 4,000 W, and a 7.5 kVA set at 0.8 delivers 6,000 W. A 25 kVA distribution transformer at 0.85 passes 21,250 W. In each case the kVA figure is the ceiling on current and the watt figure is what the load can use.

Runtime is a separate question. A 1 kVA UPS with a 900 W limit and a 100 Ah 12 V battery holds about 1.2 kWh of stored energy, so a 450 W load runs for about two and a half hours in theory and closer to two once inverter losses and derating are counted.

EquipmentRatingPower factor on the labelWatts available
Small UPS1 kVA0.9900
Small UPS1.5 kVA0.91,350
Portable generator5 kVA0.84,000
Portable generator7.5 kVA0.86,000
Distribution transformer25 kVA0.8521,250
Distribution transformer100 kVA0.880,000

Battery backed systems blur the two numbers in a useful way. An inverter is rated in VA because its output stage has a current limit, and the battery is rated in kWh because that is energy. A 2 kVA inverter with a 0.8 output power factor carries 1,600 W, and a 5 kWh pack at 90 percent depth of discharge gives about 4.5 kWh, so the pair runs a 1,600 W load for roughly two and a half hours once inverter losses are counted.

Transformer sizing carries a second constraint that the watt figure hides. Impedance and temperature rise decide how long a unit can ride out an overload, and a motor's inrush current runs six to eight times its running current for a few cycles, which looks close to a short circuit to the winding. A 25 kVA transformer that delivers 21,250 W to a steady load is not automatically the right choice for a 15 kW motor, because the starting current sets the size before the running watts do.

Why the load sets the power factor

The power factor belongs to the load, not the supply, so one 1 kVA feed can deliver anywhere from 350 W to 1,000 W depending on what is plugged into it. Induction motors are the usual cause of a low number. The Department of Energy motor systems guidebook puts an induction motor near 0.85 at full load and lower when the mechanical load falls, because the magnetising current stays roughly constant while the useful current drops away.

Modern switch mode supplies with active power factor correction run at 0.95 or better, and resistive heating runs at 1.0. The case that catches people is an oversized motor on a light job. The nameplate says 0.85, the shaft carries 30 percent of rated load, the real power factor is nearer 0.5, and a 1 kVA feed yields 500 W instead of 850 W.

LoadPower factorWatts from 1 kVA
Resistive heater1.01,000
Supply with active PFC0.98980
Motor at full load0.85850
Motor at half load0.6600
Motor at light load0.35350
Magnetic ballast lighting0.5500

Correction equipment changes the arithmetic without changing the kVA rating. A capacitor bank at the motor terminals supplies the magnetising current locally, so the supply sees a smaller apparent demand for the same watts. A plant running at 0.72 and corrected to 0.95 keeps every motor and every unit of output, while the kVA figure on the demand meter falls by about a quarter. The bank is rated in kVAR, the number this page reports next to the watts.

From watts to the electricity bill

A watt is a rate and the meter bills energy, so watts x hours / 1,000 gives kilowatt hours. An 8,000 W load for 3 hours uses 24 kWh. A 900 W load for 10 hours uses 9 kWh. At 17 cents per kWh those are $4.08 and $1.53.

The power factor stops mattering to a household bill at that point, because a residential meter charges for real energy. It starts mattering to a commercial account, where demand is often billed in kVA and a low power factor turns into a surcharge on current that did no work. The kVA to watts step is how you see how much of a demand charge is buying real output.

A demand charge example makes the point. A 60 kW load at 0.75 draws 80 kVA of demand, and the same 60 kW corrected to 0.95 draws 63.16 kVA. At $10 per kVA the correction saves $168.42 a month for equipment that already existed.

LoadWattsHourskWhCost at 17 cents
Fridge900109$1.53
Space heater1,50023$0.51
Workshop8,000324$4.08
Router12240.29$0.05

Frequently asked questions

How many watts is 1 kVA?

1 kVA is 1,000 W at a power factor of 1.0, 900 W at 0.9 and 800 W at 0.8. Multiply the kVA by 1,000 and then by the power factor of the load.

What is the kVA to watts formula?

Watts = kVA x 1,000 x power factor. For a three phase supply the same formula applies to the total kVA, and the 1.732 factor is used only when you convert to line current.

How many watts is 10 kVA?

10 kVA is 10,000 W at unity, 9,000 W at 0.9 and 8,000 W at 0.8. At 0.8 the missing 2,000 VAR is reactive power that the supply carries but the load cannot use.

Is kVA the same as kW?

No. kVA is apparent power and kW is real power, linked by the power factor. 1 kVA at 0.8 is 0.8 kW, which is 800 W.

How do I convert watts to kVA?

Divide the watts by 1,000 and then by the power factor. A 1,200 W load at 0.75 needs 1,200 / 750 = 1.6 kVA.

How many amps is 1 kVA at 120 V?

1,000 / 120 = 8.33 A on a single phase 120 V circuit, before the power factor is applied. The current for the same kVA does not depend on the power factor, but the watts it delivers do.

How do I convert three phase kVA to watts?

Multiply the total kVA by 1,000 and by the power factor. A 25 kVA three phase unit at 0.85 delivers 21,250 W, and at 480 V it draws 30.07 A per line.

Why does my 1 kVA UPS only give 600 W?

The output power factor is 0.6, which is common on older units. A modern 1 kVA UPS rated at 0.9 gives 900 W from the same apparent rating.

What power factor should I use?

1.0 for resistive heat and incandescent lamps, 0.9 to 0.98 for supplies with active power factor correction, and 0.8 for a mixed motor load. Read the nameplate when the exact figure matters.

Does kVA include time?

No. kVA is an instantaneous power rating, the same way watts are. Energy over time is measured in kWh, so an 8,000 W load running for 3 hours uses 24 kWh.

Is a 5 kVA generator enough for a 4,000 W load?

Only if the load runs at a power factor of 0.8, which puts the set at 100 percent of its rating with no margin for startup surge. A 6 kVA set leaves room for the inrush of a motor.

Can watts ever be higher than kVA?

No. Watts = kVA x 1,000 x power factor, and the power factor cannot exceed 1.0, so the watt figure is at most 1,000 times the kVA figure and usually less.

Spotted a wrong number or a broken result?

More Converters tools

See all Converters tools