kW to kVA Calculator
100 kW at a power factor of 0.8 is 125 kVA. The conversion divides by the power factor, so the same 100 kW at 0.85 pf needs 117.65 kVA and at 0.9 pf needs 111.11 kVA. Enter a voltage and the calculator adds the line current and the kvar.
| Apparent power | |
| Same apparent power in VA | |
| Real power back from kVA (check) | |
| Reactive power | |
| Line current at your voltage | |
| Current if pf were 1.0 | |
kVA = kW / power factor. Three phase line to line uses I = kVA x 1,000 / (1.7320508 x V), line to neutral uses I = kVA x 1,000 / (3 x V). All calculations run in your browser, and nothing you type is uploaded or stored.
Enter kilowatts and the power factor to get kVA, plus the line current at your voltage and phase and the kvar behind the load.
Key takeaways
- kVA = kW / power factor, so 100 kW at 0.8 pf is 125 kVA
- The two numbers are equal only at unity power factor
- At 480 volts three phase, 125 kVA draws 150.35 amps per line
- Generators, transformers and UPS units are nameplated in kVA, not kW
- Add about 25 percent headroom for motor starting before picking a size
On this page
- kW and kVA count two different things
- The formula: divide kW by the power factor
- Worked example: a 100 kW load at 0.8 power factor on 480 volts
- Worked example: a 30 kW air compressor at 0.85 power factor
- From kVA to amps: finishing the sizing job
- Sizing a generator, transformer or UPS from a kW load
- What power factor to use when the nameplate is silent
- Common mistakes when converting kW to kVA
kW and kVA count two different things
kilowatts measure real power, the part that turns a shaft, heats an element or lights a room. kilovolt-amperes measure apparent power, the full product of voltage and current that the wires, breaker and transformer must carry. The gap between the two is reactive power, and the ratio that connects them is the power factor.
Equipment nameplates rarely agree on which number they quote. A motor lists kW on its shaft rating. A generator, a transformer and a UPS list kVA, because their size is set by current, and current follows apparent power. Converting from the kW you know to the kVA you must buy is therefore the first step of any equipment selection, and it is one division long.
| Quantity | Symbol | What it does | Where it is quoted |
|---|---|---|---|
| Real power | kW | Does the actual work | Motor nameplates, heater ratings, utility energy meters |
| Apparent power | kVA | Sets the current the conductors carry | Generator, transformer and UPS nameplates |
| Reactive power | kvar | Magnetizes motors and transformers, does no work | Power factor correction equipment |
The formula: divide kW by the power factor
The conversion is one step and one direction. Apparent power is always the larger number, so the power factor goes in the denominator:
kVA = kW / power factor
Run the other way, kW = kVA x power factor. The power factor is a pure ratio with no units, and it is the same number in single phase and three phase. What changes with phase is only the current behind the kVA, which the next section covers. The U.S. Energy Information Administration defines power factor as the ratio of real power in kilowatts to apparent power in kilovolt-amperes, which is exactly this division read in reverse.
| kW load | kVA at 1.0 pf | kVA at 0.9 pf | kVA at 0.8 pf |
|---|---|---|---|
| 10 kW | 10.00 | 11.11 | 12.50 |
| 25 kW | 25.00 | 27.78 | 31.25 |
| 50 kW | 50.00 | 55.56 | 62.50 |
| 100 kW | 100.00 | 111.11 | 125.00 |
| 250 kW | 250.00 | 277.78 | 312.50 |
| 500 kW | 500.00 | 555.56 | 625.00 |
Read the table as a sizing warning. A 500 kW load at a 0.8 power factor needs 625 kVA of capacity, a quarter more than the kW figure suggests. Buying hardware on the kW number alone leaves the transformer or generator running 25 percent over its rating.
Worked example: a 100 kW load at 0.8 power factor on 480 volts
Take a shop with 100 kW of motors running at a 0.8 power factor on a 480 volt three-phase supply. The apparent power is 100 / 0.8 = 125 kVA. The line current that the panel and the feeder must carry is 125,000 / (1.7320508 x 480) = 150.35 amps per line.
The same 100 kW at unity power factor would draw only 120.28 amps, because 100,000 / (1.7320508 x 480) = 120.28. The 30 extra amps per line are reactive current: they do no work, but they heat the conductors, trip breakers and fill the transformer just the same.
| Step | Arithmetic | Result |
|---|---|---|
| Apparent power | 100 kW / 0.8 | 125.00 kVA |
| Line current, three phase | 125,000 / (1.7320508 x 480) | 150.35 A |
| Current if pf were 1.0 | 100,000 / (1.7320508 x 480) | 120.28 A |
| Reactive power | 125.00 x 0.6 | 75.00 kvar |
The kvar step uses the 3-4-5 triangle of power: at a 0.8 power factor the reactive share is 0.6 of the apparent power, so 125 kVA carries 75 kvar. Add 25 kW and 75 kvar as vectors and the result is back to 125 kVA.
Worked example: a 30 kW air compressor at 0.85 power factor
A 30 kW rotary screw compressor on a 480 volt three-phase panel is a common sizing question. At a nameplate power factor of 0.85 the apparent power is 30 / 0.85 = 35.29 kVA, and the line current is 35,294 / (1.7320508 x 480) = 42.45 amps.
That number alone does not finish the job. Compressors start loaded, and a motor starting from rest draws several times its running current for a second or two. Generators in particular need margin for that inrush, which is why the next step adds headroom before picking a model.
| Step | Arithmetic | Result |
|---|---|---|
| Apparent power | 30 kW / 0.85 | 35.29 kVA |
| Running current at 480 V | 35,294 / (1.7320508 x 480) | 42.45 A |
| With 25 percent headroom | 35.29 x 1.25 = 44.11 | 44.11 kVA |
| Nearest common generator size | round up from 44.11 | 45 kVA |
The same arithmetic on a single-phase 240 volt feed would give 35,294 / 240 = 147.06 amps, more than three times the three-phase current at the same kVA. That is the practical reason large compressors order a three-phase service.
From kVA to amps: finishing the sizing job
Once the kVA number exists, current follows from the voltage and the phase count. Single phase divides by the voltage. Three phase divides by 1.7320508 times the line-to-line voltage, or 3 times the line-to-neutral voltage.
| kVA | 480 V, 3 ph | 240 V, 3 ph | 208 V, 3 ph | 240 V, 1 ph |
|---|---|---|---|---|
| 15 kVA | 18.04 A | 36.08 A | 41.63 A | 62.50 A |
| 30 kVA | 36.08 A | 72.17 A | 83.27 A | 125.00 A |
| 45 kVA | 54.13 A | 108.25 A | 124.91 A | 187.50 A |
| 75 kVA | 90.21 A | 180.42 A | 208.18 A | 312.50 A |
| 112.5 kVA | 135.32 A | 270.63 A | 312.27 A | 468.75 A |
| 150 kVA | 180.43 A | 360.84 A | 416.36 A | 625.00 A |
The single-phase column explains why panel schedules grow so fast in small shops. The same 45 kVA that needs a 54 amp three-phase feeder needs a 187.5 amp single-phase feeder, and conductor price scales with amps.
Sizing a generator, transformer or UPS from a kW load
Three habits keep the conversion honest. First, convert every load to kVA at its own power factor before adding, because kVA values add like vectors only when the power factors match. Second, add headroom for motor starting, typically 25 percent on the largest motor. Third, round up to a standard nameplate size instead of down.
Standard dry-type transformer sizes run 15, 30, 45, 75, 112.5, 150, 225, 300, 500 and 750 kVA. Generator sets come in their own ladder, often 20, 30, 45, 100, 130, 200 and 300 kW of output, which at a 0.8 power factor corresponds to 25, 37.5, 56.3, 125, 162.5, 250 and 375 kVA of rating.
| Load | kW | pf | kVA needed | Standard size to buy |
|---|---|---|---|---|
| Small shop panel | 60 kW | 0.8 | 75.00 kVA | 75 kVA transformer |
| Workshop with compressor | 75 kW | 0.85 | 88.24 kVA | 112.5 kVA transformer |
| Machine shop, mixed motors | 100 kW | 0.8 | 125.00 kVA | 150 kVA transformer |
| Restaurant kitchen | 120 kW | 0.9 | 133.33 kVA | 150 kVA transformer |
| Small office building | 200 kW | 0.9 | 222.22 kVA | 225 kVA transformer |
| Light manufacturing | 300 kW | 0.85 | 352.94 kVA | 500 kVA transformer |
What power factor to use when the nameplate is silent
When a datasheet lists only watts, pick the power factor from the type of load. Resistive loads sit at 1.0. Induction motors land near 0.85 at full load and drift toward 0.7 when they run lightly loaded. Electronics with power factor correction sit at 0.9 or better, while uncorrected small supplies can lag to 0.6.
| Load | Typical power factor | Note |
|---|---|---|
| Heaters, incandescent lighting, ranges | 1.0 | Resistance only, no phase shift |
| Induction motor at full load | 0.80 to 0.90 | Use 0.85 when nothing better is known |
| Induction motor at half load | 0.70 to 0.80 | Oversized motors are common |
| Welders, unplated power tools | 0.60 to 0.75 | Cyclical loads, worst case at low output |
| LED drivers, computer supplies with PFC | 0.90 to 0.98 | Check the datasheet for the certified value |
The U.S. Energy Information Administration's glossary defines power factor and apparent power in exactly these terms, and the SI prefix page at NIST explains why 1 kVA is 1,000 VA. Both are worth a bookmark when a vendor's units do not match your load schedule.
Common mistakes when converting kW to kVA
Multiplying instead of dividing is the most common error, and it hides well because both answers look plausible. kVA is the larger number, so if your result came out smaller than the kW you started with, the division went the wrong way. A related slip is applying the power factor twice, once in the conversion and again in the current formula.
Using one power factor for a mixed panel is the second error. Sum the kW and the kvar separately, then rebuild the kVA, rather than averaging power factors. The third error is forgetting that the conversion says nothing about current until voltage and phase are known: 125 kVA is 150 amps at 480 volts three phase but 521 amps at 240 volts single phase.
| Mistake | What happens | Fix |
|---|---|---|
| kVA = kW x pf | Undersized transformer, trips at load | Divide by pf, do not multiply |
| Skipping pf, sizing on kW | 25 percent short at a 0.8 pf load | Always convert before comparing nameplates |
| One pf for the whole panel | kVA totals off by 10 percent or more | Sum kW and kvar separately, then combine |
| Ignoring phase in the current step | Feeder sized at a third of the needed ampacity | Apply 1.7320508 only for three phase |
The reverse direction, starting from a kVA nameplate and asking how much real power comes out, is its own tool: the kVA to kW calculator multiplies by the power factor instead of dividing. Once current is known, the voltage drop calculator checks the feeder, and the power factor calculator sizes the capacitor bank that brings a lagging load back toward unity.
Sources: the EIA glossary definition of power factor, the EIA glossary definition of apparent power, and the NIST page on SI units and prefixes for the kilo prefix.
Frequently asked questions
How do I convert kW to kVA?
Divide the kilowatts by the power factor. A 100 kW load at 0.8 pf is 100 / 0.8 = 125 kVA, and the same load at 0.9 pf is 111.11 kVA.
Why is kVA always larger than kW?
Because the power factor divides. Current leads or lags voltage in any load with magnetizing parts, so the conductors carry more apparent power than the real work done. The two numbers are equal only at a power factor of 1.0.
How many kVA is 50 kW?
At a 0.8 power factor, 62.5 kVA. At 0.85 it is 58.82 kVA and at unity it is 50 kVA. The power factor decides, so check the nameplate before sizing equipment.
How many amps is 100 kW at 480 volts three phase?
At 0.8 pf: 100 / 0.8 = 125 kVA, then 125,000 / (1.7320508 x 480) = 150.35 amps per line. At unity power factor the same load draws 120.28 amps.
Does the kW to kVA conversion change between single and three phase?
No. kVA = kW / power factor in both cases. The phase count only enters when you turn kVA into amps: three phase divides by 1.7320508 times the voltage, single phase divides by the voltage alone.
What power factor should I use if the nameplate does not list one?
Use 0.85 for motors at full load, 1.0 for resistive heaters and 0.9 for modern electronics with power factor correction. Lightly loaded motors can fall to 0.7, so a conservative 0.8 is a common planning value.
Is 1 kVA the same as 1 kW?
Only at a power factor of 1.0, which resistive loads reach. A computer supply at 0.9 pf delivers 0.9 kW per kVA, and an induction motor at 0.8 pf delivers 0.8 kW per kVA.
What size transformer do I need for a 100 kW load?
At a 0.8 power factor the load is 125 kVA, which lands on a 150 kVA standard dry-type size. At 0.9 pf it is 111.11 kVA, and 112.5 kVA is the nearest standard size above it.
How much reactive power is in 125 kVA at 0.8 pf?
125 x 0.6 = 75 kvar, because at a 0.8 power factor the reactive share is 0.6 of the apparent power. Check it with the 3-4-5 triangle: 100 squared plus 75 squared is 15,625, and its square root is 125.
Why do utilities bill in kVA?
Conductor and transformer losses follow current, and current follows apparent power. Billing demand in kVA charges a customer for the capacity consumed, so a lagging power factor costs money even when the kWh total is unchanged.
Can I add kVA ratings from several loads directly?
Only when the power factors match. kVA values at different power factors add as vectors, so sum the kW and the kvar separately and take the square root of their squares to get the combined kVA.
What is the difference between this and a kVA to kW calculator?
Direction. This page divides kW by the power factor to size equipment in kVA. The kVA to kW calculator multiplies a nameplate kVA by the power factor to find the real power a unit can deliver.
Spotted a wrong number or a broken result?
More Tech tools
- Amp-Hour Calculator
- Amps to kVA Calculator
- Audio File Size Calculator: WAV, MP3 and Storage Time
- Bandwidth Calculator
- Battery Charge Time Calculator
- Battery Life Calculator
- Bits to Bytes Converter
- CFM Calculator
- Capacitance
- Capacitor Calculator
- Current Calculator
- Data Transfer Calculator
- Data Usage Calculator
- Download Time Calculator
- Downtime Cost Calculator
- Electric Charge Calculator
Fee schedules, rates and rules change without notice. Always confirm important figures with the official source before you rely on them.