100 kW at a power factor of 0.8 is 125 kVA. The conversion divides by the power factor, so the same 100 kW at 0.85 pf needs 117.65 kVA and at 0.9 pf needs 111.11 kVA. Enter a voltage and the calculator adds the line current and the kvar.

Enter kilowatts and the power factor to get kVA, plus the line current at your voltage and phase and the kvar behind the load.

By the Lelifi editors ·

Key takeaways

kVA needed to carry a 100 kW load, by power factor166.670.60pf142.860.70pf133.330.75pf125.000.80pf117.650.85pf111.110.90pf105.260.95pf100.001.00pfkVA
The kVA needed to carry 100 kW climbs from 100 to 166.67 as the power factor falls from 1.0 to 0.6.
Line current at 480 volts three phase, by kVA size60.1450 kVA90.2175 kVA120.28100 kVA150.35125 kVA180.42150 kVAamps
Line current at 480 volts three phase rises from 60.14 amps at 50 kVA to 180.43 amps at 150 kVA.
On this page
  1. kW and kVA count two different things
  2. The formula: divide kW by the power factor
  3. Worked example: a 100 kW load at 0.8 power factor on 480 volts
  4. Worked example: a 30 kW air compressor at 0.85 power factor
  5. From kVA to amps: finishing the sizing job
  6. Sizing a generator, transformer or UPS from a kW load
  7. What power factor to use when the nameplate is silent
  8. Common mistakes when converting kW to kVA

kW and kVA count two different things

kilowatts measure real power, the part that turns a shaft, heats an element or lights a room. kilovolt-amperes measure apparent power, the full product of voltage and current that the wires, breaker and transformer must carry. The gap between the two is reactive power, and the ratio that connects them is the power factor.

Equipment nameplates rarely agree on which number they quote. A motor lists kW on its shaft rating. A generator, a transformer and a UPS list kVA, because their size is set by current, and current follows apparent power. Converting from the kW you know to the kVA you must buy is therefore the first step of any equipment selection, and it is one division long.

QuantitySymbolWhat it doesWhere it is quoted
Real powerkWDoes the actual workMotor nameplates, heater ratings, utility energy meters
Apparent powerkVASets the current the conductors carryGenerator, transformer and UPS nameplates
Reactive powerkvarMagnetizes motors and transformers, does no workPower factor correction equipment

The formula: divide kW by the power factor

The conversion is one step and one direction. Apparent power is always the larger number, so the power factor goes in the denominator:

kVA = kW / power factor

Run the other way, kW = kVA x power factor. The power factor is a pure ratio with no units, and it is the same number in single phase and three phase. What changes with phase is only the current behind the kVA, which the next section covers. The U.S. Energy Information Administration defines power factor as the ratio of real power in kilowatts to apparent power in kilovolt-amperes, which is exactly this division read in reverse.

kW loadkVA at 1.0 pfkVA at 0.9 pfkVA at 0.8 pf
10 kW10.0011.1112.50
25 kW25.0027.7831.25
50 kW50.0055.5662.50
100 kW100.00111.11125.00
250 kW250.00277.78312.50
500 kW500.00555.56625.00

Read the table as a sizing warning. A 500 kW load at a 0.8 power factor needs 625 kVA of capacity, a quarter more than the kW figure suggests. Buying hardware on the kW number alone leaves the transformer or generator running 25 percent over its rating.

Worked example: a 100 kW load at 0.8 power factor on 480 volts

Take a shop with 100 kW of motors running at a 0.8 power factor on a 480 volt three-phase supply. The apparent power is 100 / 0.8 = 125 kVA. The line current that the panel and the feeder must carry is 125,000 / (1.7320508 x 480) = 150.35 amps per line.

The same 100 kW at unity power factor would draw only 120.28 amps, because 100,000 / (1.7320508 x 480) = 120.28. The 30 extra amps per line are reactive current: they do no work, but they heat the conductors, trip breakers and fill the transformer just the same.

StepArithmeticResult
Apparent power100 kW / 0.8125.00 kVA
Line current, three phase125,000 / (1.7320508 x 480)150.35 A
Current if pf were 1.0100,000 / (1.7320508 x 480)120.28 A
Reactive power125.00 x 0.675.00 kvar

The kvar step uses the 3-4-5 triangle of power: at a 0.8 power factor the reactive share is 0.6 of the apparent power, so 125 kVA carries 75 kvar. Add 25 kW and 75 kvar as vectors and the result is back to 125 kVA.

Worked example: a 30 kW air compressor at 0.85 power factor

A 30 kW rotary screw compressor on a 480 volt three-phase panel is a common sizing question. At a nameplate power factor of 0.85 the apparent power is 30 / 0.85 = 35.29 kVA, and the line current is 35,294 / (1.7320508 x 480) = 42.45 amps.

That number alone does not finish the job. Compressors start loaded, and a motor starting from rest draws several times its running current for a second or two. Generators in particular need margin for that inrush, which is why the next step adds headroom before picking a model.

StepArithmeticResult
Apparent power30 kW / 0.8535.29 kVA
Running current at 480 V35,294 / (1.7320508 x 480)42.45 A
With 25 percent headroom35.29 x 1.25 = 44.1144.11 kVA
Nearest common generator sizeround up from 44.1145 kVA

The same arithmetic on a single-phase 240 volt feed would give 35,294 / 240 = 147.06 amps, more than three times the three-phase current at the same kVA. That is the practical reason large compressors order a three-phase service.

From kVA to amps: finishing the sizing job

Once the kVA number exists, current follows from the voltage and the phase count. Single phase divides by the voltage. Three phase divides by 1.7320508 times the line-to-line voltage, or 3 times the line-to-neutral voltage.

kVA480 V, 3 ph240 V, 3 ph208 V, 3 ph240 V, 1 ph
15 kVA18.04 A36.08 A41.63 A62.50 A
30 kVA36.08 A72.17 A83.27 A125.00 A
45 kVA54.13 A108.25 A124.91 A187.50 A
75 kVA90.21 A180.42 A208.18 A312.50 A
112.5 kVA135.32 A270.63 A312.27 A468.75 A
150 kVA180.43 A360.84 A416.36 A625.00 A

The single-phase column explains why panel schedules grow so fast in small shops. The same 45 kVA that needs a 54 amp three-phase feeder needs a 187.5 amp single-phase feeder, and conductor price scales with amps.

Sizing a generator, transformer or UPS from a kW load

Three habits keep the conversion honest. First, convert every load to kVA at its own power factor before adding, because kVA values add like vectors only when the power factors match. Second, add headroom for motor starting, typically 25 percent on the largest motor. Third, round up to a standard nameplate size instead of down.

Standard dry-type transformer sizes run 15, 30, 45, 75, 112.5, 150, 225, 300, 500 and 750 kVA. Generator sets come in their own ladder, often 20, 30, 45, 100, 130, 200 and 300 kW of output, which at a 0.8 power factor corresponds to 25, 37.5, 56.3, 125, 162.5, 250 and 375 kVA of rating.

LoadkWpfkVA neededStandard size to buy
Small shop panel60 kW0.875.00 kVA75 kVA transformer
Workshop with compressor75 kW0.8588.24 kVA112.5 kVA transformer
Machine shop, mixed motors100 kW0.8125.00 kVA150 kVA transformer
Restaurant kitchen120 kW0.9133.33 kVA150 kVA transformer
Small office building200 kW0.9222.22 kVA225 kVA transformer
Light manufacturing300 kW0.85352.94 kVA500 kVA transformer

What power factor to use when the nameplate is silent

When a datasheet lists only watts, pick the power factor from the type of load. Resistive loads sit at 1.0. Induction motors land near 0.85 at full load and drift toward 0.7 when they run lightly loaded. Electronics with power factor correction sit at 0.9 or better, while uncorrected small supplies can lag to 0.6.

LoadTypical power factorNote
Heaters, incandescent lighting, ranges1.0Resistance only, no phase shift
Induction motor at full load0.80 to 0.90Use 0.85 when nothing better is known
Induction motor at half load0.70 to 0.80Oversized motors are common
Welders, unplated power tools0.60 to 0.75Cyclical loads, worst case at low output
LED drivers, computer supplies with PFC0.90 to 0.98Check the datasheet for the certified value

The U.S. Energy Information Administration's glossary defines power factor and apparent power in exactly these terms, and the SI prefix page at NIST explains why 1 kVA is 1,000 VA. Both are worth a bookmark when a vendor's units do not match your load schedule.

Common mistakes when converting kW to kVA

Multiplying instead of dividing is the most common error, and it hides well because both answers look plausible. kVA is the larger number, so if your result came out smaller than the kW you started with, the division went the wrong way. A related slip is applying the power factor twice, once in the conversion and again in the current formula.

Using one power factor for a mixed panel is the second error. Sum the kW and the kvar separately, then rebuild the kVA, rather than averaging power factors. The third error is forgetting that the conversion says nothing about current until voltage and phase are known: 125 kVA is 150 amps at 480 volts three phase but 521 amps at 240 volts single phase.

MistakeWhat happensFix
kVA = kW x pfUndersized transformer, trips at loadDivide by pf, do not multiply
Skipping pf, sizing on kW25 percent short at a 0.8 pf loadAlways convert before comparing nameplates
One pf for the whole panelkVA totals off by 10 percent or moreSum kW and kvar separately, then combine
Ignoring phase in the current stepFeeder sized at a third of the needed ampacityApply 1.7320508 only for three phase

The reverse direction, starting from a kVA nameplate and asking how much real power comes out, is its own tool: the kVA to kW calculator multiplies by the power factor instead of dividing. Once current is known, the voltage drop calculator checks the feeder, and the power factor calculator sizes the capacitor bank that brings a lagging load back toward unity.

Sources: the EIA glossary definition of power factor, the EIA glossary definition of apparent power, and the NIST page on SI units and prefixes for the kilo prefix.

Frequently asked questions

How do I convert kW to kVA?

Divide the kilowatts by the power factor. A 100 kW load at 0.8 pf is 100 / 0.8 = 125 kVA, and the same load at 0.9 pf is 111.11 kVA.

Why is kVA always larger than kW?

Because the power factor divides. Current leads or lags voltage in any load with magnetizing parts, so the conductors carry more apparent power than the real work done. The two numbers are equal only at a power factor of 1.0.

How many kVA is 50 kW?

At a 0.8 power factor, 62.5 kVA. At 0.85 it is 58.82 kVA and at unity it is 50 kVA. The power factor decides, so check the nameplate before sizing equipment.

How many amps is 100 kW at 480 volts three phase?

At 0.8 pf: 100 / 0.8 = 125 kVA, then 125,000 / (1.7320508 x 480) = 150.35 amps per line. At unity power factor the same load draws 120.28 amps.

Does the kW to kVA conversion change between single and three phase?

No. kVA = kW / power factor in both cases. The phase count only enters when you turn kVA into amps: three phase divides by 1.7320508 times the voltage, single phase divides by the voltage alone.

What power factor should I use if the nameplate does not list one?

Use 0.85 for motors at full load, 1.0 for resistive heaters and 0.9 for modern electronics with power factor correction. Lightly loaded motors can fall to 0.7, so a conservative 0.8 is a common planning value.

Is 1 kVA the same as 1 kW?

Only at a power factor of 1.0, which resistive loads reach. A computer supply at 0.9 pf delivers 0.9 kW per kVA, and an induction motor at 0.8 pf delivers 0.8 kW per kVA.

What size transformer do I need for a 100 kW load?

At a 0.8 power factor the load is 125 kVA, which lands on a 150 kVA standard dry-type size. At 0.9 pf it is 111.11 kVA, and 112.5 kVA is the nearest standard size above it.

How much reactive power is in 125 kVA at 0.8 pf?

125 x 0.6 = 75 kvar, because at a 0.8 power factor the reactive share is 0.6 of the apparent power. Check it with the 3-4-5 triangle: 100 squared plus 75 squared is 15,625, and its square root is 125.

Why do utilities bill in kVA?

Conductor and transformer losses follow current, and current follows apparent power. Billing demand in kVA charges a customer for the capacity consumed, so a lagging power factor costs money even when the kWh total is unchanged.

Can I add kVA ratings from several loads directly?

Only when the power factors match. kVA values at different power factors add as vectors, so sum the kW and the kvar separately and take the square root of their squares to get the combined kVA.

What is the difference between this and a kVA to kW calculator?

Direction. This page divides kW by the power factor to size equipment in kVA. The kVA to kW calculator multiplies a nameplate kVA by the power factor to find the real power a unit can deliver.